beautypg.com

User scaling, 4function description, 2 configuration – Pilz PSSu E S 4AI U User Manual

Page 22

background image

4.2

Configuration

4

Function description

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

4-6

Analogue value and typical digital value with a voltage range of
0 ... +10 V plus default values:

4.2.1.4

User scaling

User scaling

4-

][Funktionsbeschreibung_BA_Konfig Skalier Anwend Ein

User scaling is a second level of scaling. You can use this scaling to cor-

rect local influences. The function is the same as that of manufacturer

scaling, but a different value is used for amplification factor 1:

y = (a

2

/ 256

D

* x) + b

2

or

y = (a

2

/ 100

H

* x) + b

2

a

2

= Amplification factor * 256

D

User scaling is deactivated in the default setting. The default value for

offset is 0. The default value for gain is 256

D

(100

H

). That corresponds

to amplification factor 1.

Key:

y: Digital value after user scaling

x: Digital value before user scaling

a

2

: Gain

b

2

: Offset

a

2

/ 1024

D

: Amplification factor

Analogue value of voltage

Hexadecimal digital value

Decimal digital value

0 V

0

0

5 V

4000

16 384

10 V

7FFF

32 767

5 V

6 V

7 V

8 V

9 V

4 V

3 V

2 V

1 V

0 V

10 V

32 767

29 490

26 214

22 937

19 660

16 384

13 107

9 830

6 553

3 277

0