Neuron Tools Errors Guide
13
LCL#
Description
7
The encoded value for the device's clock input of
supported range of
An invalid encoded clock value has been used to describe the hardware
clock speed. See LCL#2.
8
The encoded value for the channel's minimum clock rate of
the supported range of
An invalid encoded clock value has been specified for the channel's
minimum clock speed. This value originates from the standard transceiver
database, and the presence of this problem indicates a corrupted or
incorrect database record. Verify that your standard transceiver database
(stdxcvr.xml) has not been corrupted. Re-install the product and choose the
Repair option when prompted.
9
Unable to compute media access control values (raw transceiver data): the
specified Neuron clock frequency is too high for the transceiver [LCL#9]
This error condition is unavoidable for some combinations of (typically)
high Neuron clock rates and (typically) slow channels. A different
operating mode of the same transceiver or a lower Neuron clock rate might
solve the problem.