Echelon Neuron User Manual
Page 136
128
Neuron Exporter Errors (NEX)
NEX#
Description
21
Unable to compute device's Communication Parameters [NEX#21]
Unable to compute device’s communication parameters. Verify device clock
speed and transceiver preferences.
22
Out of memory while creating file '
Out of memory when creating an output file. See error message for failure
details.
23
Cannot find file '
Cannot find a required file. Attempt to fix with rebuild.
24
Cannot create file '
Cannot create a file. Verify that the media is writable and the destination
folder has not been write-protected.
25
Cannot read file '
Cannot read from a file. Attempt to fix with rebuild.
26
Cannot write file '
Cannot write to a file. Verify that the media is writable and the
destination folder has not been write-protected.
27
Unable to copy file '
Unable to copy a file. Verify that the media is writable and the destination
folder has not been write-protected.
28
XIF version is
[NEX#28]
Cannot process the external interface file due to outdated version. See
error message for failure details. Rebuilding unconditionally should fix this
by creating an up-to-date version 4 XIF file.
29
Line
[NEX#29]
Bad external interface file, field count mismatch. See error message for
failure details. Attempt to fix with rebuild.
30
NV '
[NEX#30]
Bad external interface file, NV field count mismatch. See error message for
failure details. Attempt to fix with rebuild.