Lcl errors – Echelon Neuron User Manual
Page 20
12
Communication Parameter Calculator Errors (LCL)
LCL Errors
Table 5 lists the LCL error codes.
Table 5. LCL Error Codes
LCL#
Description
1
Can not compute communication port control byte. [LCL#1]
The tool failed to compute the communication port (CP) control byte.
Verify that your standard transceiver database (stdxcvr.xml) has not been
corrupted. Re-install the product and choose the Repair option when
prompted.
2
Unrecognized encoded clock rate value
An unrecognized encoded value was for clock speed (5 for 10MHz, 6 for
20MHz, and so on). Re-install the product and choose the Repair option
when prompted.
3
The transceiver's general purpose data record seems malformed:
[LCL#3]
The xcvr_gp_data in STDXCVR.XML seems malformed. Verify that your
standard transceiver database (stdxcvr.xml) has not been corrupted. Re-
install the product and choose the Repair option when prompted.
4
The device's clock rate (encoded value
communication rate (encoded value
clock divider value. One of the two input rates might be invalid [LCL#4]
The device's clock rate and the transceiver's communication rate result in
an invalid communication clock divider value. One of the two input rates
might be invalid. See the error message for failure details. Try increasing
or lowering the Neuron clock speed.
5
Unable to determine
The aspect described as
communication parameter calculations. Verify that your standard
transceiver database (stdxcvr.xml) has not been corrupted. Re-install the
product and choose the Repair option when prompted.
6
The transceiver requires a minimum clockrate which is higher than the device's
configured input clock speed. [LCL#6]
The target chip’s system clock speed for the MAC context is lower than the
required minimum for this transceiver. Choose a higher clock rate where
possible, or choose a different transceiver type.