Project Make Errors (PMK)

PMK#

Description

119

Cannot determine default firmware version for image :

reason> [PMK#119]

Failure to determine the firmware version to use as a default. The file
'default.ver', normally contained in the \Lonworks\images folder (on

whichever drive your LonWorks folder resides) could be missing or could be

corrupt. As a workaround, you can explicitly specify the firmware version
in the target device preferences, do not use 'Default' as a firmware version.

120

Cannot determine set of standard libraries from :

[PMK#120]

Failure to determine standard neuron libraries from . Verify
that (a text file), which defaults to

\Lonworks\images\Stdlibs.lst, is present and is not corrupt.

121

Cannot determine transceiver type. Verify preferences in device template and

project. [PMK#121]

Failure to determine the transceiver type. The project file and/or device
template file might be corrupt. Edit these files and correct the transceiver

preferences, specifying an explicit transceiver type (other than 'Default'), if

needed.

122

Cannot calculate signature, [PMK#122]

The external interface signature cannot be calculated. This indicates
missing or corrupt intermediate files (.BIF and .BF2 extensions), or missing

or corrupt explicit XIF appendix files (XF2 extension). Verify the project
and device preferences, and attempt to build unconditionally.

124

Unknown macro switch record received from (try performing

unconditional build). [PMK#124]

Internal error: switch uses invalid macro value. To fix, attempt the "clean"

and "build unconditionally" commands and

125

Cannot compute dependency code for DRF catalog and program ID

(LDRF error ). Verify that your LDRF catalog is valid and up-to-

date. [PMK#125]

The LDRF catalog cannot be accessed. Use the Resource Editor utility to

make sure the catalog file is present and intact. The catalog file defaults to
LonWorks\Types\ldrf.cat (on whichever drive your LonWorks folder

resides). If the catalog file is missing, attempt to re-create one by using the
MKCAT.EXE utility, that is available for download from the

www.lonmark.org

website.

126

Malformed min/max model number specified in . Correct preferences or

disable automatic program ID management. [PMK#126]

The program ID data given in the NB device template file appears
malformed. Edit and correct the preferences using NodeBuilder's device

template file editor, or disable automatic program ID management.