beautypg.com

Dunkirk Excelsior EXB Series User Manual

Page 59

background image

59

21.6 Conventional Expansion Tank (Not

Provided)

In a properly assembled system, expanding water flows

into an expansion tank.
• Expansion tank should be sized correctly because im-

properly installed or sized expansion tank may result in

frequent lifting of relief valve or other heating system

problems.

• It is important to install tank higher than top of boiler.

Connecting pipe from boiler to expansion tank shall rise

continuously up to expansion tank so that air can rise

into expansion tank.

• Expansion tank is partially filled with air. Air compresses

as water expands, thus forming an air pressure cushion.

This “spring-like” cushion serves to maintain correct op-

erating water pressure regardless of water temperature.

This assures a “full measure” of water, even in highest

radiation unit of the system.

• Tank also serves as trap for excess air in the system. Air

can cause noises in pipes and inefficient circulation in

radiators if left in piping system.

• It is possible for a tank to become “waterlogged” (filled

with water). It can also become overfilled with air when

filling system with new water. Fittings on tank and in line

to tank are for bleeding off excess air and water.

21.7 Diaphragm Expansion Tank (Not Provided)

Diaphragm type expansion tank takes place of conventional

expansion tank.
• Carefully read instructions packed with your tank

assembly. Expansion tank should be sized and installed

correctly. Improperly installed or sized expansion tank

may result in frequent lifting of relief valve or other

heating system problems.

• Tank typically comes with 10-12 psi air charge. Same as

pressure produced in system by automatic fill valve set

to fill boiler to 10-12 psi with fresh water. When system

is first filled, tank will fill partially with water. As water is

heated, and system pressure increases, water expands

into tank and compresses air in the tank. This compressed

air cushion permits water in the system to expand as

temperature changes and assures “full measure” of water,

even in highest radiation unit of system.

• Diaphragm type expansion tank can be mounted on air

purger fitting or at any other convenient place in supply

or return line. It is recommended to locate diaphragm

type expansion tank in supply line with circulator located

after expansion tank. This configuration allows circulator

to “pump away” from expansion tank for improved air

elimination and system performance.

• Air eliminator fitting or air purger is not provided. Air

eliminator fitting or air purger is used to help remove

air from system before it reaches radiators. It should be

installed in supply line. Air left in system can cause noises

in pipes and inefficient circulation in radiators.

21.1 Limit Relay Control (provided)

Water temperature limit control in limit relay is adjustable.

See Limit instructions for how to set limit temperature.

21.2 Drain Valve (provided)

Drain valve is manually operated valve, means of draining

all water from boiler and heating system. Installed in

casting below burner door.

21.3 Circulator

• Forced hot water systems require circulator.
• Separate circulator or zone valve is required for each

zone, if there are two or more zones. Circulator must

have capacity to provide circulation required by heating

system.

• Circulator should be connected to supply main and

must be wired into boiler’s electrical system. “9 - Boiler

System Piping” on page 18, for piping configurations

with circulator located on supply main piping using zone

circulators or zone valves.

• When piping is arranged with zone circulators and no

bypass piping, circulator provided with boiler may be

used as zone circulator. Both piping arrangements allow

circulator to pump away from expansion tank and show

how piping should be arranged to allow heating system to

be easily purged of air.

• Circulator can be installed on return side of boiler, if

preferred.

21.4 Main Air Vent: (Not Provided)

Before system is filled with water, there is air in pipes and

radiation units. Some air will be trapped as system is filled.

It is possible to eliminate most of this air through air vents

on radiation units. Main air vent will speed and simplify this

process. Main air vent should be installed on highest point

in supply main.

21.5 Automatic Fill Valve (Not Provided)

Hot water system must be filled with water. Adding new

water, when needed can be done manually (by use of hand

valve in water supply line). This requires regular attention

to system’s needs. Automatic fill valve or pressure reducing

valve accomplishes this without attention. Install in supply

line on hot water boilers only. Valve operates through

water pressure differentials. It does not require electrical

connection.

21 - EQUIPMENT AND ACCESSORIES