beautypg.com

Warning – Dunkirk Excelsior EXB Series User Manual

Page 11

background image

11

1.

Determine volume of space (boiler room). Rooms

communicating directly with the space in which

appliances are installed, through openings not furnished

with doors, are considered a part of the space.

Volume (ft

3

) = Length (ft.) x Width (ft.) x Height (ft.)

2.

Determine total input of all appliances in the space.

Add inputs of all appliances in the space and round the

result to the nearest 1000 BTU/hr.

3.

Determine type of space. Divide Volume by total input

of all appliances in space. If the result is greater than

or equal to 50 ft

3

/1000 BTU/hr, then it is considered

an unconfined space. If the result is less than 50

ft

3

/1000 BTU/hr, then the space is considered a

confined space.

4.

When a boiler is located in an unconfined space of a

conventionally constructed building, fresh air infiltration

through cracks around windows and doors normally

provides adequate air for combustion and ventilation.

5.

Provide outdoor air for boiler located in a confined

space or an unconfined space in a building of unusually

tight construction. Outdoor air may be provided with

the use of two permanent openings which communicate

directly or by duct with the outdoors or spaces

(ventilated crawl or attic) freely communicating with

the outdoors. Locate one opening within 12 inches

of top of space. Locate remaining opening within 12

inches of bottom of space. Size each opening per the

following:

A. Direct communication with outdoors:

Minimum free area of 1 square inch per 4,000 BTU

per hour input of all equipment in space.

B. Vertical Ducts: Minimum free area of 1 square

inch per 4,000 BTU per hour input of all equipment

in space. Duct cross-sectional area shall be same

as opening free area.

C. Horizontal Ducts: Minimum free area of 1 square

inch per 2,000 BTU per hour input of all equipment

in space. Duct cross-sectional area shall be same

as opening free area.

Alternate method for boiler located within

confined space: Use indoor air if two permanent

openings communicate directly with additional space(s)

of sufficient volume such that the combined volume of

all spaces meet criteria for unconfined space. Size each

opening for minimum free area of 1 square inch per

1,000 BTU per hour input of all equipment in spaces,

but not less than 100 square inches.

6.

Louvers and Grilles of Ventilation Ducts

A. All outside openings should be screened and

louvered. Screens used should not be smaller than

1/4 inch mesh. Louvers will prevent the entrance of

rain and snow.

B. Free area requirements need to consider the

blocking effect of louvers, grilles or screens

protecting the openings. If the free area of the

louver or grille is not known, assume wood louvers

have 20-25% free area and metal louvers and grilles

have 60-75% free area.

C. Louvers and grilles must be fixed in the open

position, or interlocked with the equipment to open

automatically during equipment operation.

Figure 3 - Air Openings For Boiler Located In

Confined Space (Utility Room)

7 - FRESH AIR FOR COMBUSTION

WARNING

Asphyxiation, fire hazard. Do not obstruct air

openings to combustion area. Follow instructions

below, to maintain adequate combustion air.

!

NOTICE

Install outside air intake if used with a fireplace or

kitchen or bathroom exhaust fan. These devices rob

boiler and water heater of combustion air.