12.1 Antifreeze added to boilers must be nontoxic,

and must be of type specifically intended for use in closed

hydronic heating systems. Under no circumstances should

automotive antifreeze be used. Antifreeze used in any

boiler may reduce capacity by 10% or more and increase

fuel consumption. See Table 6 and 7.

Table 6 - BOILER WATER VOLUMES

Number of

Boiler Section

Total Volume

(Gallons)

4

3.6

5

4.3

6

5.1

7

5.9

Table 7 - PIPING WATER VOLUMES

PIPE SIZE

COPPER

PIPE

FACTOR

STEEL PIPE

FACTOR

½”

82.5

63.5

¾”

40.0

36.0

1”

23.3

22.2

1 ¼”

15.3

12.8

1 ½”

10.8

9.5

2”

6.2

5.8

Divide total length of piping in feet by

appropriate factor in table to determine volume

in gallons.