Figure 34 - Limit

16 - OPERATING THE BOILER - SYSTEM START-UP

16.1 Setting The Limit Control

Setting can be verified using TEST/SETTINGS button.

See Page 41.

16.2 Setting High Limit

To adjust, turn HI TEMP dial

A

until desired setting is

displayed. See Figure 34. Overall range of High limit setting

is from 100°F to 220°F (82° C to 104° C). High limit

(HL) on limit control is factory set at 190°F. Temperature

setting may be varied to suit requirements of installation.

Differentials are automatic and will vary based on control

settings and boiler temperature.

16.3 Setting Low Limit

• Low limit is designed to maintain temperature in boilers

equipped with tankless coils used for domestic hot

water. Low limit is factory set to OFF.

• For cold start operation, low limit must be turned to

OFF.

16.4 Setting Economy Feature (See Figure 35)

• Economy feature is factory set for 1 zone heating

system. To adjust, turn ECONOMY dial

D

until number

displayed equals number of heating zones.

• Do not include indirect water heaters in number of

heating zones.

• Economy feature conserves fuel by reducing boiler

temperature. If heating system is unable to supply

needed heat to house, ECONOMY dial should be turned

to lower setting. (example: in a three zone house, turn

dial to 2 or 1).

• Conversely, if boiler provides adequate heat, added

fuel savings can be achieved by selecting higher setting

(example: 4 or 5).

• If heating and indirect water heater signals were not

separated when wiring the control, Economy feature

should be turned off to ensure the boiler supplies

adequate temperature to heat indirect tank.

16.5 Setting Zone/Indirect Switch

When installing with indirect water heater, zone/indirect

switch must be set in the I position, calls to ZC-ZR will

bypass thermal targeting feature and allow boiler to fire to

high limit setting to heat indirect tank.
Indirect signal must be separate from all heating zone

signals.
If you choose not to separate indirect signal from heating

zones, turn off economy feature to ensure boiler supplies

adequate temperature to indirect tank.

Figure 35 - Setting Economy Feature

SETTING

OFF

Disables economy function. Will allow boiler to

fire until hi-limit temp is reached and re-fire

with a 10° subtractive differential.

LO

Provides lowest level of fuel savings. Use this

setting only if the house does not stay warm at

higher settings.

1

Recommended setting for single zone systems.

2

Recommended setting for Two zone systems.

3

Recommended setting for Three zone systems.

4

Recommended setting for Four zone systems.

5

Recommended setting for Five zone systems.

HI

Provides highest level of fuel savings.