beautypg.com

Dunkirk Excelsior EXB Series User Manual

Page 46

background image

46

Figure 39 - Beckett Electrode Tip Adjustments

Standard Dimensions (L1, V1) Heads

Figure 40 - Beckett Electrode Tip Adjustments

Standard Dimensions (L2) Heads

17 - OIL BURNER, NOZZLE, & AIR SETTINGS

Figure 41 - Beckett Check/Adjust “Z”

Dimensions L1 & L2 Heads

Figure 42 - Beckett Check/Adjust ‘Z’ Dimension -

V1 Heads

L1/L2 Heads
See Figure 39. The important “Z” dimension is distance

from leading edge of head to end of air tube. This distance

for L1 & L2 heads is 1-3/8” if the tube has a straight shroud

or 1-3/4” if air tube has conic shroud. “Z” dimension is fac-

tory set for burners shipped with air tube installed. Even if

factory set, verify “Z” dimension has not been changed.

1.

Use following procedure to adjust “Z” dimension, if it is

not correct:

• Turn off power to burner.
• Disconnect oil connector tube from nozzle line.
• Refer to figure above. Loosen splined nut from nozzle

line. Loosen hex head screw securing escutcheon

plate to burner housing.

• Place end of ruler at leading edge of head and, using

straight edge across end of airtube, measure distance

to end of tube. A Beckett T501 gauge may also be

used.

• Slide nozzle line forward or back until this dimension

is 1-3/8” for L1 & L2 heads if tube has straight

shroud, or 1-3/4” if air tube has conic shroud.

• Tighten hex head screw to secure escutcheon plate to

burner chassis. Then tighten splined nut and attach

oil connector tube.

2.

Recheck “Z” dimension periodically when servicing to

ensure escutcheon plate has not been moved. Reset

“Z” dimension if you replace air tube or nozzle line

assembly.

V1 heads
See Figure 40. The important “Z” dimension is distance

from leading edge of head to end of air tube. This distance

for V1 heads is 1-¾”. “Z” dimension is factory set for

burners shipped with air tube installed. Even if factory set,

verify “Z” dimension has not been changed.

1.

Use following procedure to adjust “Z” dimension, if it is

not correct:

• Turn off power to burner.
• Disconnect oil connector tube from nozzle line. Refer

to figure above. Loosen splined nut from nozzle line.

Loosen hex head screw securing escutcheon plate to

burner housing.

• Loosen acorn nut. Move head adjusting plate until

“0” lines up with reference indicator on housing, and

tighten hex head screw. Place end of ruler at leading

edge of head and, using straight edge across end of

air tube, measure distance to end of tube. A Beckett

T501 gauge may also be used.

• Slide the nozzle line forward or back until this

dimension is 1-¾” for V1 heads. Tighten acorn nut.

• Tighten hex head screw to secure head adjusting

plate to burner chassis. Then tighten splined nut and

attach oil connector tube.

2.

Recheck “Z” dimension periodically when servicing to

ensure escutcheon plate has not been moved. Reset

“Z” dimension if you replace air tube or nozzle line

assembly.