19.1 Oil Boiler Cleaning Instructions

1.

Clean flueways. Figure 46, Page 56.

A. Shut off power to burner.
B. Access to combustion chamber, remove swing door

bolts. If boiler is equipped with flexible fuel line(s),

swing door open.

C. Remove vent connector.
D. Remove liners & baffles (if equipped) from flue

passages. Baffles are installed in 3rd pass (two inner

flue ways.)

E. Clean 3rd Pass – Insert 2” Dia. x 42” long wire or fiber

bristle brush into each of two 3rd passes. Using long

strokes, push brush all the way through boiler until

brush has exited the smoke box opening.

Pull brush all the way forward until it has exited front

of boiler.
Continue this operation for entire height of flue way

until clean. Repeat operation for other 3rd pass flue

way.

F. Clean 2nd Pass – Insert wire or fiber bristle brush into

each of two 2nd passes. Using long strokes, push

brush all the way through boiler until brush hits back

wall of reversing chamber. Pull brush all the way

forward until it has exited front of boiler.

Continue operation for entire height of flue way until

clean. Repeat operation for other 2nd pass flue way.

G. Do not start burner unless burner swing door and vent

connector are secured in place.

H. Clean passage from combustion chamber to 2nd pass.
I. Vacuum loose debris in bottom of combustion chamber

and smoke box.

2.

Clean combustion chamber and baffles. Use wire

or fiber bristle brush to clean surfaces of combustion

chamber and baffles. Vacuum all of loose debris in

bottom of combustion chamber.

3.

After cleaning: Vacuum all remaining debris as

necessary. Inspect burner swing door insulation, and

rope gasket for signs of damage. If damaged, replace

as needed.

4.

Re-assemble boiler.

A. Insert liner and baffles (if equipped) into correct flue

way. Baffles are installed in 3rd pass. (Two inner flue

ways)

B. Inspect chimney and clean if necessary.
C. Clean and re-attach vent connector onto rear of the

boiler with three screws.

NOTICE

When securing burner swing door verify door is

drawn-in equally on both sides. Do not overtighten

door bolts. Rope gasket will provide sufficient seal

when door is snugged into place.

D. Tighten swing door hardware to provide adequate

seal to rope gasket around perimeter of door. Use

alternating tightening method from non-hinged side to

hinged side cap screws to pull door tight equally.

19 - OIL BOILER / BURNER CLEANING INSTRUCTIONS

WARNING

Fire, burn, asphyxiation hazard. Turn off service

switch to boiler to prevent accidental firing of

burner outside combustion chamber. Disconnect

burner power cord from wire harness in front jacket.

Tighten swing door fastener completely when

service is complete. Failure to follow instructions in

this manual and understand all requirements could

result in death or serious injury.

!

19.2 Oil Burner Cleaning Instructions

Consult burner manufacturer’s instructions.

WARNING

Asphyxiation hazard. A clean and unobstructed

chimney flue is necessary to allow noxious fumes

that could cause injury or loss of life to vent safely.

Inspect periodically throughout heating season for

any obstructions. Failure to follow instructions in

this manual and understand all requirements could

result in death or serious injury.

!

NOTICE

Connect boiler to approved chimney in good

condition. Property damage could result if boiler is

connected to dirty or inadequate chimney. Inspect

interior of chimney flue and clean before start of

heating season.

DANGER

Before servicing, turn off electrical power to boiler

at service switch. Turn off fuel supply to burner.

Failure to comply will result in death or serious

injury.

!