Table 8 -

Recommended Minimum Chimney Sizes

FIRING RATE

(gph)

CHIMNEY

HEIGHT (ft)

NOMINAL

CHIMNEY

ROUND

LINER INSIDE

SQUARE

LINER

INSIDE

0.60 -1.30

15

8” x 8”

6”

6 ¾” x 6 ¾”

1.31 -1.80

15

8” x 8”

7”

6 ¾” x 6 ¾”

1.81 -2.00

20

8” x 8”

8”

6 ¾” x 6 ¾”

For elevations above 2,000 feet above sea level, add 3 feet to the chimney heights.

14.1 Chimney Venting

Oil fired boilers with connections to vents or chimneys,

vent installation shall conform to requirements of

authority having jurisdiction or in absence of such

requirements NFPA 31 Installation Of Oil Burning

Equipment (U.S.) or CSA B139 (Canada) and

applicable provisions of local building codes.

Installation shall conform to requirements of

NFPA31 – Standard for the Installation of Oil-

Burning Equipment and NFPA 211 – Standard for

Chimneys, Fireplaces, Vents, and Solid Fuel-Burning

Appliances for installations and requirements of CSA

B139 – Installation Code for Oil-burning Equipment.

(Installations in Canada).

1.

Ensure sufficient draft during heating season to allow

for safe evacuation of flue gasses.

2.

Boiler can be vented into fireclay tile-lined masonry

chimney or type L vent or factory built chimney that

complies with type HT requirements of UL103. See

Figure 32, Page 37.

3.

Chimney Inspection – Prior to installation of any new or

replacement fuel burning equipment chimney shall be

inspected by qualified service agency.
A. De-rating may cause condensation on interior

walls of chimney and boiler. Loose mortar can be

indication of history of condensing flue gases upon

inside walls of chimney. Do not install chimney until

it meets requirements of NFPA 211 or CSA B139.

B. Unlined Chimney – Do not install boiler if chimney

is constructed of brick only. Only approved clay

liners or listed chimney lining systems shall be used

as specified in NFPA 31 or CSA B139.

C. Abandoned Openings – Seal Openings through

chimney wall that are no longer used in accordance

to NFPA 211.

D. Clean Chimney – Chimney shall be free of all loose

debris.

4.

Install draft regulator at least 18” above breech; 18”

of straight run up-stream of regulator ensures proper

operation.

5.

Draft Regulator – Use supplied draft regulator with this

appliance. Do not use any other draft regulator. See
Figure 31, Page 37.

14 - CHIMNEY AND VENTING CONNECTIONS