1.

Inspect Installation Before Starting Burner.
A. Verify venting, water piping, oil piping, and

electrical system are installed properly. Refer to

installation Instructions contained in this manual.

B. Confirm all electrical, water and oil supplies

are turned off at source and vent is clear from

obstructions.

2.

Fill Heating System With Water.
A. Failure to clean system can result in clogged air

vents, circulator damage and seized zone valves.

Clean heating system if boiler water is dirty. Refer to “18 -

Maintenance” on page 53 for proper cleaning instructions

for water boilers.

Fill entire heating system with water and vent air from

system.

Use following procedure on series loop or multi-zoned

system installed as per piping diagrams, to remove air

from system when filling:

A. Close shut off valve in boiler system piping

between air separator and vertical purge valve.

B. Isolate all zones by closing zone valves or shut-off

valves in supply and return of each zone(s).

C. Attach hose to vertical purge valve in boiler system

supply piping. Terminate hose in five gallon bucket

or suitable floor drain or outdoor area.

D. Starting with one zone at a time, open zone valve

or shut-off valve in boiler supply and return piping.

E. Open purge valve.
F. Open shut-off valve in cold water supply piping.
G. When zone is completely purged of air, close zone

valve or shut-off valve. Open valve to next zone

to be purged. Repeat this step until all zones have

been purged. At completion, open all valves.

H. Close purge valve, continue filling system until

pressure gauge reads 12 psi. Close shut-off valve

in cold water supply piping.

I. Open shut off valve in boiler system piping.
J. Remove hose from purge valve.
K. Confirm boiler and system have no water leaks.

L. It may be necessary to clean air vent assembly

after few days of operation.

3.

Check controls, wiring and burner. Verify all

connections are tight and burner is rigid, all electrical

connections have been completed and fuses installed,

and oil tank is filled and oil lines have been tested.

15 - FILLING BOILER

WARNING

Fire, burn, asphyxiation hazard. Turn off service

switch to boiler to prevent accidental firing of

burner outside combustion chamber. Disconnect

burner power cord from wire harness in front jacket.

Tighten swing door fastener completely when

service is complete. Failure to follow instructions in

this manual and understand all requirements could

result in death or serious injury.

!

NOTICE

Boiler maximum operating pressure is posted on

ASME data label located on front lower leg of boiler.

Never exceed this pressure. Do not plug relief

valve.