NOTICE

Before starting or resetting control from restricted

lockout state, troubleshoot heating system for root

cause(s) of lockout.

8.

Genisys Control - Resetting From Restricted

or Hard Lockout.

A. Make necessary repairs or adjustment to ensure

safe start condition.

B. Ensure appliance is free of oil and oil vapors

before starting or resetting burner

C. If control continues to lock out without satisfied call for

heat, or fails motor relay check, control enters Hard

(restricted) Lockout in order to limit accumulation of

unburned oil in combustion chamber.

D. To reset, hold button down for 15 seconds until red

light turns off and yellow light turns on.

E. Always verify control functions according to

specifications before leaving installation site.

F. Replace control if it does not operate as specified.

9.

Genisys Control - Disable Function

Anytime burner is running, press and hold reset button to

disable burner. Burner will remain off as long as button is

held.

WARNING

Remove jumper after following check.

!

16.10 Check High Temperature Limit Control

.

Jumper thermostat terminals. Allow burner to operate until

shut down by limit. Installation is not considered complete

until this check has been made.

16.11 Test Low Water Cut-Off Operation.

See

Figure 36, Page 41.

16.12 If Controls Do Not Meet Requirements

replace control and repeat checkout procedures.

16.13 Nozzles And Electrodes:

Use proper size,

spray angle, and spray pattern nozzle.

A. Refer to “17 - Oil Burner, Nozzle, & Air Settings” on

page 44.

B. To install nozzle, remove nozzle line electrode

assembly, if necessary remove retention ring

assembly, install and tighten nozzle. Be careful not to

damage electrode insulators or bend electrode tips.

16 - OPERATING THE BOILER - SYSTEM START-UP

C. After installing nozzle, reassemble nozzle line

electrode assembly and set electrode tip spacing.

D. Electrode tip spacing may need to be set prior to

reassembling nozzle line electrode assembly. Refer

to figures on following pages for setting electrode tip

spacing on Beckett.

16.14 Check Thermostat Operation:

Thermostat

location has important effect on operation of boiler system.

A. Follow instructions included with your thermostat.

Typically, thermostat is located about five feet above

floor on inside wall.

B. Thermostat should be located to sense average room

temperature.

Table 10 - Thermostat locations to Avoid

DEAD

SPOTS

HOT SPOTS

COLD SPOTS

Behind

doors

Concealed pipes

Concealed pipes

or ducts

Fireplace

TV sets

Stairwell drafts

Corners &

alcoves

Radios

Door drafts

Lamps

Unheated room

on other side of

wall

Direct sunlight

Kitchens

C. Verify room temperature reaches selected

temperature setting, thermostat should turn boiler’s

burner off, and once room temperature falls few

degrees boiler starts operating again.