Figure 36 - LED Legend

1

TEMP

ACTIVE Indicates Limit Control is

powered and temperature function is active.

2

TEMP

HI TEMP Illuminates when boiler water

temperature reaches high limit setting. Remains

lit until water temperature falls 10°F. Limit control

prevents burner operation while this LED is on. See

Differential explanation page 39.

3

LWCO

ACTIVE Indicates low water cut-off

(LWCO) function of limit control is active. Boiler

is factory equipped with Hydrolevel electro-well,

enabling control’s low water cut-off function. LED will

be on at all times when control is powered.

Important: If control well is replaced with a well

other than Electro-Well, LED will not illuminate

indicating control is not providing low water cut-off

functionality.

WARNING

Burn and scald hazard. Do not add water until boiler

has fully cooled. Failure to follow these instructions

could result in death or serious injury.

!

4

LWCO

LOW WATER Illuminates if boiler is in

low water condition. Limit control will prevent burner

operation during this condition.

Important: System must be checked by a qualified

service agency prior to resuming operation.

5

ECONOMY

ACTIVE Indicates thermal targeting

function is active and limit control will reduce boiler

temperature to conserve fuel. Economy feature is

activated using the Economy dial. See “How Thermal

Targeting Works” this page.

16 - OPERATING THE BOILER - SYSTEM START-UP

6

ECONOMY

TARGET Economy feature is active,

limit control continually sets target temperatures

below high limit setting to maximize fuel efficiency.

When boiler water reaches target temperature, LED

illuminates and burner shuts down. Boiler water will

continue to circulate and heat the house as long as

thermostat call continues. LED will stay lit until boiler

temperature drops below differential set point at

which point boiler will be allowed to fire again.

Note: LED illuminates regularly during normal boiler

operation.

7

TEST/SETTINGS Button

To Test Low Water Cut-Off: Press and hold Test/

Settings button for 5 seconds. Display will read LCO.

LWCO TEST

LCO

Red Low Water light should illuminate and burner circuit

(B1 and B2) should de-energize. Note: Control must be in-

stalled with Electro-Well for low water cut-off functionality.

To View Current Settings: Press and release Test/

Settings button in short intervals to sequentially display the

following settings:

Display will return to boiler temperature (default) if Test/

Settings button is not pressed for 5 seconds.