Dunkirk Excelsior EXB Series User Manual
Page 51
51
Table 16: RIELLO 40BF DIRECT VENT PRELIMINARY BURNER SETTINGS
Boiler Model
Head
Type
Inser-
tion
Depth
Firing
Rate
[GPH]
Com-
bustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pres-
sure
[PSI]
Head
Setting
Air
Setting
Pressure
Switch
Setpoint
Rated
AFUE
Efficiency
[%]
4075
Reverse
2.75"
0.75
Oval
Delavan 0.65x60W
150
3
5.0
0.25" WC
86.0
4095
Standard
1.75"
0.95
Oval
Delavan 0.75x90B
175
1
4.0
0.25" WC
85.0
4110
Standard
1.75"
1.10
Oval
Delavan 1.00x90B
125
2
5.0
0.25" WC
84.0
5100
Standard
2.75"
1.00
None
Delavan 0.75x60B
175
1
5.0
0.80" WC
86.5
5115
Standard
1.75"
1.15
None
Delavan 1.00x80B
130
2
5.8
0.80” WC
85.0
5135
Standard
1.75"
1.35
None
Delavan 1.20x80B
125
4
5.8
0.80” WC
84.0
6130
Standard
2.75"
1.30
V6
Delavan 1.00x45B
175
2
8.0
0.90" WC
86.5
Timings
Pre-purge
12 seconds
Post-Purge
45 seconds
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
Table 16 - Riello 40BF (DIRECT VENT) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test
instruments.
Boiler
Model
Riello
Oil
Burner
Model
ECR Oil Burner
Part Number
4075
40BF3
240007528
4095
40BF5
240009407
4110
40BF5
240009408
5100
40BF5
240007529
5115
40BF5
240009409
5135
40BF5
240009410
6130
40BF5
240007530