beautypg.com

Dunkirk Excelsior EXB Series User Manual

Page 18

background image

18

9.1

Connect System Supply And Return Piping

To Boiler

Connect system supply and return piping to correct

boiler fittings.
Size system circulator to supply sufficient flow (GPM)

to allow 20°F temperature differential in system.
When sizing system circulator, use single most

restrictive zone to determine maximum pressure

drop

.

1.

Boiler used in connection with refrigeration systems,

install boiler so chilled medium is piped in parallel with

heating boiler using appropriate valves to prevent

chilled medium from entering boiler. See Figure 28,

Page 31.

2.

If boiler is connected to heating coils located in air

handling units exposed to refrigerated air, equip boiler

piping with flow control valves to prevent gravity

circulation of boiler water during operation of cooling

system.

3.

Limit control includes low water cutoff function, sensing

water level at control well in top of the rear boiler

section. Periodic inspection and testing is necessary

per instructions provided with limit control.

4.

When installation of boiler is for new heating system,

install all radiation units (panels, radiators, baseboard,

or tubing) and supply and return mains. After heating

system piping and components have been installed,

make final connection of system piping to boiler.

Recommend mount circulating pump on supply side

piping, such that it pumps away from expansion tank.

5.

Hot water boiler installed above radiation level must

be equipped with low water cut off device. This boiler

is factory equipped with low water cutoff. Periodic

inspection is necessary, per manufacturer’s specific

instructions.

6.

When connecting cold water supply to pressure

reducing valve, make sure clean water supply is

available. When water supply is from well or pump,
install sand strainer at pump.

9.2 Bypass Piping

See Piping Diagrams for illustrations for this section.
Bypass piping may be required for applications listed

below. Failure to do so may cause damage due to thermal

shock and sustained condensation within the boiler.
Protect boiler from sustained operation of return water

temperatures lower than 130°F (54C). Occasionally,

temperatures as low as 70°F (21C) may return back to

boiler when a zone that has not been activated for some

time is opened. However, most residential systems with

finned-tube (aluminum-copper) baseboard radiation

contain low volume of water and will not adversely affect

boiler. Systems with finned-tube baseboard radiation

typically do not require bypass.
Bypass piping details shown in piping diagrams must be

used for any one of following conditions:

• All large water content systems, including cast iron

standing radiators, cast iron baseboard, converted

two-pipe steam systems, converted gravity circulation

systems and other similar systems.

• Any system, including finned-tube baseboard, with

priority domestic hot water zone.

Install ¾ inch bypass line as shown in piping diagrams for

systems identified above.
Bypass valve cannot protect boiler from sustained

condensing operation for low temperature applications such

as radiant floor heating. These types of system require

active controls that prevent return of cold return water to

boiler.
Refer to Radiant Professional’s Alliance (RPA)

www.radiantprofessionalsalliance.org for piping

recommendations for non-condensing boiler applications.

9 - BOILER SYSTEM PIPING