16 - OPERATING THE BOILER - SYSTEM START-UP

16.6 Activating Thermal Pre-Purge (optional)

Activation of this feature is not recommended for boilers

with tankless coils.

• Limit has thermal pre-purge feature to maximize

efficiency. When activated, control will purge higher

boiler temperatures down to 135°F at start of any

thermostat call and supply latent energy in boiler to

heating zone calling.

• During purge cycle, display will indicate PUR.
• If heat is not sufficient to satisfy thermostat, control will

energize burner.

• Feature works with single and multi-zone heating

systems utilizing circulators or zone valves. No change

in wiring is needed.

To Activate Thermal Pre-Purge

1.

Push and hold TEST/SETTINGS button for 20 seconds.

2.

Display will read PURR On.

3.

To deactivate feature, push and hold button a second

time for 20 seconds.

4.

Display will read PURR OFF.

16.7 Control Action On System Start-Up

At initial start-up, with economy feature active, control

establishes 145°F target temperature. To test high limit

shut-off function, economy dial must be turned to off.
Once tested, restore economy setting.
If heating demand is high, target will increase over time to

satisfy heat load.
To reduce potential for condensing, control will allow boiler

to heat to 120°F prior to energizing the circulator.

16.8 How Thermal Targeting Works

Thermal targeting technology analyzes thermostat activity

and continually evaluates how much heat the house

requires.
When it is very cold outside, heat demand is high and limit

control will raise boilers target temperature to provide heat.
When outside temperature is mild, heat demand is low.

Limit control will lower boiler’s target temperature saving

fuel.