Table 1 — physical data (cent) – Carrier 48TJ016-028 User Manual
Page 8
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 1 — Physical Data (cent)
UNIT 48TJ
016D/F
020D/F
024D/F
028D/F
FURNACE SECTION
Rollout Switch Cutout Temp (F)+
190
190
190
190
Burner Orifice Diameter (in... .drill size)
Natural Gas
0.1285...30/0.136...29
0.1285...30/0.136...29
0.1285...30/0.136...29
0.1285...30/0.136...29
Thermostat Heat Anticipator Setting (amps)
208/230, 575
Stage 1
0.98
0.98
0.98
0.98
Stage 2
0.44
0.44
0.44
0,44
460
V
stage
1
0.80
0.80
0.80
0,80
Stage 2
0.44
0.44
0.44
0,44
Gas Input
Stage 1
172,000/225,000
206,000/270,000
206,000/270,000
206,000/270,000
Stage 2
230,000/300,000
275,000/360,000
275,000/360,000
275,000/360,000
Efficiency (Steady State) {%)
81
81
81
81
Temperature Rise Range
Manifold Pressure (in. wg)
15-45/20-50
15-45/20-50
15-45/20-50
15-45/20-50
Natural Gas
3.3
3.3
3.3
3.3
Gas Valve Quantity
1
1
1
1
Field Gas Connection Size (in
.-FPT)
3/4
3/4
3/4
3/4
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)__________________
426
320
LOW-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)__________________
27
44
FREEZE PROTECTION THERMOSTAT (F)
Opens
Closes
30 ±5
45 ±5
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
Cleanable
2.. .20x25x 1
1.. .20x 20 x1
RETURN-AIR FILTERS
Quantity...Size (in.)
Throwaway*’'
4.. .20x20x2
4.. .16x20x2
POWER EXHAUST
V
2
Hp, 208/230-460
V
Motor Direct Drive, Propeller-Fan (Factory-Wired for 460 v)
LEGEND
Bhp
™ Brake Horsepower
TXV
— Thermostatic Expansion Valve
'Circuit 1 uses the lower portion of condenser coil and lower portion of evap
orator coils; and Circuit 2 uses the upper portion of both coils.
fRollout switch is manual reset.
**The 48TJ028 units requires 2-in. industrial-grade filters capable of handling
face velocities of up to 625 ft/min (such as American Air Filter no, 5700 or
equivalent).
NOTE: The 48TJ016-028 units have a low-pressure switch (standard) located
on the suction side.