Carrier 48TJ016-028 User Manual
Page 34
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 18 — Fan Performance — 48TJF020 and 024 (High Heat Units)
AVAILABLE EXTERNAL STATIC PRESSURE (iti, wg)
AiHFLOW
(cfm)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5,500
795
2,43
2043
866
2.74
2306
934
3.07
2578
998
3.40
2856
1059
3.74
3142
1117
4.08
3434
6,000
854
2,92
2452
921
3.24
2722
984
3.57
3998
1044
3,90
3281
1102
4.25
3570
1158
4.60
3865
6,500
914
3,46
2909
977
3.79
3184
1036
4.12
3465
1093
4.46
3752
1148
4.81
4045
1201
5.16
4343
7,000
975
4.06
3414
1034
4.39
3695
1090
4.73
3981
1144
5.08
4272
1196
5.43
4569
1246
5.79
4870
7,500
1037
4.72
3969
1092
5.06
4255
1145
5.41
4546
1196
5.76
4842
1256
6.12
5142
1294
6.48
5447
8,000
1099
5,44
4575
1150
5,79
4866
1201
6.14
5162
1249
6.50
5462
1297
6,86
5766
1343
7.22
6075
8,500
1161
6,22
5232
1210
6,57
5529
1258
6.93
5829
1304
7.29
6134
1349
7,66
6443
1393
8.03
6755
9,000
1223
7,07
5943
1270
7,43
6245
1315
7.79
6550
1360
8.16
6869
1403
8.53
7171
1445
8.90
7487
9,500
1286
7,98
6708
1331
8.34
7014
1374
8.71
7324
1416
9.08
7638
1457
9.46
7954
1498
9.84
8274
10,000
1349
8.95
7528
1392
9.32
7839
1433
9.70
8154
1473
10.07
8471
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(cfm)
1.4
1.6
1.8
1.9
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5,500
1173
4.44
3732
1227
4.80
4036
1279
5.17
4345
1304
5.35
4502
1329
5,54
4629
6,000
1211
4.95
4165
1263
5.32
4471
1313
5.69
4782
1337
5.87
4939
1361
6,06
5097
6,500
1252
5,53
4646
1302
5.89
4954
1350
6.26
5267
1373
6.56
5425
1396
6.64
5584
7,000
1295
6.16
5176
1343
6.52
5487
1389
6.90
5802
1412
7.09
5961
1434
7.28
6121
7,500
1340
6.85
5756
1386
7.22
6070
1431
7.60
6387
1452
7.79
6547
1474
7.98
6709
8,000
1388
7.60
6388
1431
7.97
6704
1474
8.35
7024
1495
8.54
7186
1516
8.74
7348
8,500
1436
8.41
7071
1478
8.79
7390
1520
9.17
7713
1540
9.37
7876
_
_
_
9,000
I486
9.28
7807
1527
9.67
8130
_
_
_
_
_
_
_
_
_
9,500
1538
10.22
8597
—
—
—
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
„
—
„
—
„
LEGEND
Bhp — Brake Horsepower
Flop — Factory-Installed Option
Watts
— Input Watts to Motor
NOTES;
1.
Standard low-medium static drive range for the 020 size is 910 to
1095 rpm. Standard low-medium static drive range for the 024 size is
1002 to 1225 rpm. Alternate high-static drive range for the 020 size is
1069 to 1287. Alternate high-static drive range for the 024 size is 1193 to
1458 rpm. Other rpms require a tield-supplied drive.
2,
Maximum continuous bhp tor the 020 size is 5.90. Maximum continuous
bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (460 v). The maximum
continuous watts for the 020 size is 5180. The maximum continuous
watts for the 024 size is 7915 (208/230, 575 v) or 8640 (460 v). Do not
adjust motor rpm such that motor maximum bhp and/or watts is
exceeded at the maximum operating dm.
3.
Static pressure losses (i.e., economizer) must be added to external static
pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5.
Fan performance is based on wet coils, clean filters, and casing losses.
See Tables 21-23 for accessory/FlOP static pressure information.
6.
Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi
dence. Using fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
7.
Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details.
Table 19 — Fan Performance — 48TJF028 (High Heat Units)
AVAfLABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(cfm)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
992
4.05
3,348
1051
4.44
3,668
1106
4.83
3995
1160
5.24
4331
1212
5.65
4675
1262
6.08
5026
7,500
1055
4.77
3,947
1110
5.17
4,277
1162
5.58
4615
1214
6.00
4960
1263
6.43
5312
1311
6.86
5672
8,000
1118
5.58
4,610
1170
5.99
4,950
1220
6.41
5298
1268
6.84
5653
1315
7.27
6014
1361
7.72
6382
8,500
1182
6,46
5,339
1231
6.88
5,690
1278
7.31
6047
1324
7.75
6411
1369
8,20
6782
1413
8.66
7158
9,000
1246
7,42
6,136
1292
7.86
6,498
1337
8.30
6865
1381
8.75
7239
1424
9,21
7618
1466
9.68
8003
9,500
1310
8,47
7,005
1354
8.92
7,377
1397
9.38
7754
1439
9.84
8137
1480
10,31
8525
1520
10.79
8918
10,000
1374
9.61
7,947
1416
10.07
8,329
1457
10.54
8715
1497
11.02
9107
1537
11.50
9504
—
—
—
10,500
1439
10.84
8,964
1479
11.32
9,356
1518
11.79
9752
—
—
—
—
—
—
—
—
—
11,000
1503
12.17
10,059
1542
12.65
10,460
—
—
—
—
—
—
—
—
—
—
—
—
11,250
1536
12.86
10,636
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
(cfm)
1.4
1.6
1.8
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
1311
6.51
5385
1359
6.96
5751
1405
6.00
6124
7,500
1358
7.30
6039
1403
7.76
6412
1448
6.84
6792
8,000
1406
8.17
6767
1560
8.63
7137
1492
7.75
7524
8,500
1456
9.12
7541
1498
9.59
7929
1539
8.75
8323
9,000
1507
10.15
8393
1548
10.63
8790
—
—
—
9,500
—
—
—
—
—
—
—
—
—
10,000
—
—
—
—
—
—
—
—
—
10,500
11,000
11,250
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower
Flop
— Factory-Installed Option
Watts
— Input Watts to Motor
NOTES:
1,
Standard low-medium static drive range is 1066 to 1283 rpm. Alternate
high-static drive range is 1332 to 1550. Other rpms require a field-
supplied drive.
2.
Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (460 v) and
the maximum continuous watts are 9510 (208/230, 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or
watts is exceeded at the maximum operating cfm.
3.
Static pressure losses (i.e,, economizer) must be added to external static
pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5.
Fan performance is based on wet coils, clean filters, and casing losses.
See Tables 21-23 for accessory/FlOP static pressure information.
6.
Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi
dence, Using fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
7.
Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details.
34