Legend and notes for fig. 58 and 59 – Carrier 48TJ016-028 User Manual
Page 47
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

LEGEND AND NOTES FOR FIG. 58 AND 59
LEGEND
AHA
— Adjustable, Heat Anticipator
SN
— Sensor
BKR W/AT
— Breaks with Amp Turns
TB
— Terminal Block
C
— Contactor, Compressor
TC
— Thermostat Cooling
CAP
— Capacitor
TH
— Thermostat Heating
CB
— Circuit Breaker
TRAN
— Transformer
CC
— Cooling Compensator
CLO
— Compressor Lockout
COMP
— Compressor Motor
DM
— Damper Motor
DU
— Dummy Terminal
EQUIP
— Equipment
FPT
— Freeze Protection Thermostat
FU
— Fuse
GND
— Ground
HPS
— High-Pressure Switch
lAQ
— Indoor Air Quality Sensor
IDM
— Induced-Draft Motor
IFM
— Indoor-Fan Motor
IGC
— Integrated Gas Unit Controller
L
— Light
LED
— Light Emitting Diode
LPS
— Low-Pressure Switch
LS
— Limit Switch
MGV
— Main Gas Vaive
NEC
— National Electrical Code
OAT
— Outdoor Air Temperature Sensor
OCCUP
— Occupancy Sensor
OFC
— Outdoor-Fan Contactor
OFM
— Outdoor-Fan Motor
PL
— Plug Assembly
PMR
— Phase Monitor Relay
QT
— Quadruple Terminal
RAT
— Return Air Temperature Sensor
RS
— Rollout Switch
<; >
Terminal (Marked)
Q
Terminal (Unmarked)
I I
Terminal Block
9
Splice
----------- Factory Wiring
—
Field Control Wiring
---------- Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
°' °
Economizer Motor
— R e m o t e POT Field Accessory
;
OAT Sensor
Disch Air Sensor
; RAT Accessory Sensor
Low Ambient Lockout Switch
NOTES:
1. Compressor and/or tan motor(s) thermally protected three phase motors protected against primary
single phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with Type 90° C or its
equivalent.
3. TRAN1 is wired for 230-v operation. If unit is 208 v, disconnect the black wires from the ORN TRAN
wire and reconnect to the RED TRAN wire. Apply wirenuts to wires.
4. CB1,2 Must Trip Amps are equal to or less than 156% FLA. IFCB 140%.
5. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices;
before replacing CLO check these devices.
6. Jumpers are omitted when unit is equipped with economizer.
7. Number(s) indicates the line iocation of used contacts. A bracket over (2) numbers signifies a single
pole, double throw contact. An underlined number signifies a normally closed contact. Plain (no line)
number signifies a normally open contact.
8. Remove Jumper between RC and RH.
9. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb.
10. If a separate field-supplied 24 v transformer is used for the lAQ sensor power supply, it cannot have the
secondary of the transformer grounded.
11. OAT sensor is shipped inside unit and must be relocated in the field for proper operation.
12. For field-installed remote minimum position POT. remove black wire jumper between P and PI and set
control minimum position POT to the minimum position.
47