Table 20 — Air Quantity Limits
UNIT
48TJ
MINIMUM
COOLING
CFM
MINIMUM
HEATING CFM
MAXIMUM
CFM
Low Heat
High Heat
016
4500
3800
3800
7,500
020
5400
4750
5450
9,000
024
6000
4750
5450
10,000
028
7000
4750
5450
11,250
Table 21 — Accessory/FlOP Static Pressure*
(In. wg) —48TJ016
COMPONENT
CFM
4500
5000
6000
7200
7500
Economizer
0.04
0.05
0.07
0.09
0.10
LEGEND
Flop — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should then be used in conjunction with the Fan Per
formance tables to determine biower rpm and watts.
Table 22 — Accessory/FlOP Static Pressure*
(In. wg) — 48TJ020-028
COMPONENT
CFM
5000
6000
7200
9000
10,000
11,250
Economizer
0.06
0.07
0.09
0.11
0.12
0.14
LEGEND
Flop — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the
evaporator entering-air cfm should then be used in conjunction with the Fan Perfor
mance tables to determine blower rpm and watts.
Table 23 — MolstureMISer’'“ Dehumldlflcatlon
Package Static Pressure Drop (In. wg)
UNIT SIZE
UNIT NOMINAL
CFM PER TON
TONS
300
400
500
48TJ016
15
.040
.071
.111
48TJ020
18
.058
.102
.160
48TJ024
20
.071
.126
.197
48TJ028
25
.111
.197
.308
Table 24 — Fan Rpm at Motor Pulley Settings*
48TJ
0
1/2
1
li/j
2
2
i/j
3
3i'a
4
41/j
5
5i'a
6
016(208/230, 460 v)t
tt
tt
1179
1150
1121
1093
1064
1035
1006
978
949
920
891
016 (208/230, 460
V)“
tt
tt
1559
1522
1488
1455
1422
1389
1356
1323
1289
1256
1227
016(575 v)t
tt
tt
1429
1403
1376
1349
1323
1296
1269
1242
1215
1188
1159
020t
tt
tt
1095
1077
1058
1040
1021
1002
984
965
947
928
910
020**
tt
tt
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
024t
tt
tt
1225
1209
1187
1165
1143
1120
1098
1076
1053
1031
1002
024**
tt
tt
1458
1434
1407
1381
1354
1328
1301
1275
1248
1222
1193
028t
tt
tt
1283
1269
1247
1225
1203
1182
1160
1138
1116
1095
1066
028**
tt
tt
tt
tt
1551
1524
1497
1470
1443
1415
1388
1361
1332
‘Approximate fan rpm shown,
flndicates standard drive package.
“Indicates alternate drive package.
ttDue to belt and pulley size, pulley cannot be set to this number of
turns open.
NOTE: For
required.
speeds not listed above, field-supplied drives are