Table 16 — Fan Performance — 48TJD028 (Low Heat Units)
AVAiLABLE EXTERNAL STATIC PRESSURE (in. wg)
AIHFLOW
(cfm)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
941
3.35
2769
1002
3.80
3140
1061
4.27
3528
1117
4.76
3934
1171
5.27
4356
1224
5.80
4794
7,500
999
4,05
3348
1057
4.53
3742
1112
5,02
4152
1166
5.54
4579
1218
6,07
5020
1268
6.63
5478
8,000
1058
4.85
4007
1113
5.35
4424
1165
5.87
4856
1216
6.41
5304
1266
6.97
5766
1314
7.55
6243
8,500
1117
5.74
4750
1169
6.28
5190
1219
6.83
5645
1268
7.40
6114
1315
7.98
6597
1361
8.58
7094
9,000
1177
6.75
5583
1226
7.31
6047
1274
7.89
6524
1320
8.48
7015
1365
9.09
7520
1410
9.72
8037
9,500
1237
7.98
6511
1284
8.46
6999
1329
9.07
7499
1374
9.69
8012
1417
10.33
8538
1459
10.98
9076
10,000
1297
9.12
7450
1342
9.74
8051
1385
10.37
8574
1428
11,02
9110
1469
11.68
9657
1510
12.36
10217
10,500
1358
10.49
8674
1400
11.14
9209
1442
11.80
9755
1483
12,47
10314
1523
13.16
10883
—
—
—
11,000
1418
12.00
9919
1459
12.67
10478
_
_
_
_
_
_
_
_
_
_
_
_
11,250
1449
12.80
10585
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
AIHFLOW
(cfm)
1.4
1.6
1.8
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
7,000
1274
6.35
5248
1323
6.92
5718
1371
5.54
6204
7,500
1316
7.20
6960
1364
7.79
6437
1410
6.41
6939
8,000
1360
8.14
6734
1406
8.76
7239
1450
7.40
7759
8,500
1406
9.20
7605
1449
9.83
8129
1492
8.48
8666
9,000
1453
10.36
8568
1495
11.02
9111
1536
9.69
9667
9,500
1501
11.64
9627
1541
12.32
10190
—
—
—
10,000
_
_
_
_
_
_
_
_
_
10,500
_
_
_
_
_
_
_
_
_
11,000
—
—
—
—
—
—
—
—
—
11,250
—
—
—
—
„
—
—
LEGEND
Bhp
— Brake Horsepower
Flop
— Factory-Installed Option
Watts
— Input Watts to Motor
NOTES;
1.
Standard low-medium static drive range Is 1066 to 1283 rpm. Alternate
high-static drive range is 1332 to 1550. Other rpms require a field-
supplied drive.
2.
Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (460 v) and
the maximum continuous watts are 9510 (208/230, 575 v) or 11,000
(460 v). Do not adjust motor rpm such that motor maximum bhp and/or
watts is exceeded at the maximum operating cfm.
3. Static pressure losses (i.e., economizer) must be added to external static
pressure before entering Fan Performance table,
4. Interpolation is permissible. Do not extrapolate.
5.
Fan performance is based on wet coils, clean filters, and casing losses.
See Tables 21-23 for accessory/FlOP static pressure information,
6.
Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi
dence. Using fan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details.
Table 17 — Fan Performance — 48TJF016 (High Heat Units)
AVAILABLE EXTERNAL STATIC PRESSURE (iri. wg)
AIHFLOW
(cfm)
0.2
0.4
0,6
0.8
1.0
1.2
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
819
1.55
1335
914
1.76
1518
1001
1.98
1705
1083
2.20
1894
1160
2.42
2088
1234
2.65
2284
4800
861
1.78
1538
951
2.00
1726
1035
2.22
1916
1113
2.45
2110
1188
2.68
2307
1259
2.91
2507
5100
904
2,04
1759
989
2,26
1952
1069
2,49
2147
1145
2,72
2345
1218
2.95
2545
1287
3.17
2749
5400
947
2,32
1999
1028
2,55
2197
1105
2,78
2396
1179
3,01
2598
1248
3.25
2802
1315
3.49
3009
5700
990
2,62
2259
1068
2,85
2461
1142
3,09
2665
1213
3,33
2871
1280
3.57
3079
1345
3.81
3289
6000
1034
2.94
2539
1109
3.18
2745
1180
3.42
2953
1248
3.67
3163
1313
3.91
3375
1376
4.16
3589
6300
1078
3.29
2840
1150
3.54
3050
1218
3.78
3262
1284
4.03
3476
1348
4.28
3692
_
_
_
6600
1123
3.67
3161
1192
3.91
3376
1258
4.16
3592
—
—
—
—
—
—
—
—
—
6900
1167
4.06
3504
1234
4.32
3723
—
—
—
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AVAILABLE EXTERNAL STATIC PRESSURE (irt. wg)
AIHFLOW
(cfm)
1.4
1.6
1.8
1.9
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
1304
2,88
2484
1371
3,12
2688
1435
3.36
2895
1467
3.48
2999
1497
3.60
3104
4800
1327
3.14
2711
1393
3.38
2917
1456
3.62
3126
1486
3.75
3232
1517
3.87
3338
5100
1353
3.43
2955
1417
3.67
3165
1478
3.92
3377
1508
4.04
3484
1537
4.16
3592
5400
1380
3.73
3219
1442
3.98
3432
1502
4.23
3646
1531
4.35
3755
—
—
—
5700
6000
6300
1408
4.06
3503
1468
4.31
3718
-
—
—
-
—
—
—
-
—
6600
6900
7200
—
—
—
—
—
—
-
—
—
-
—
-
LEGEND
Bhp
— Brake Horsepower
Flop
— Factory-Installed Option
Watts
— Input Watts to Motor
NOTES:
1
Standard low-medium static drive range is 891 to 1179 rpm (for 208/230
and 460-v units) or 1159 to 1429 rpm (for 575-v units). Alternate high-
static drive range is 1227 to 1550 (for 208/230 and 460-v units). The
alternate high-static drive is not available for 48TJ016 575-v units. Other
rpms require a field-supplied drive.
Maximum continuous bhp is 4.25 (208/230 and 460 v) or 3.45 (575 v)
and the maximum continuous watts are 3775 (208/230 and 460 v) or
3065 (575 v). Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
3. Static pressure losses (i.e., economizer) must be added to external static
pressure before entering Fan Performance table.
4. Interpolation is permissible. Do not extrapolate.
5.
Fan performance is based on wet coils, clean filters, and casing losses.
See Tables 21-23 for accessory/FlOP static pressure information.
6.
Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi
dence. Using tan motors up to the watts or bhp rating shown will not
result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
7. Use of a field-supplied motor may affect wiring size. Contact your Carrier
representative for details.
33