Table 13 — co, Sensor standard settings – Carrier 48TJ016-028 User Manual
Page 29
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 13 — CO
2
Sensor Standard Settings
SETTING
EQUIPMENT
OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Interface with Standard
Building Control System
Proportional
Any
0-1 ov
4-20 mA
0-2000
1000
50
2
Proportional
Any
2-1 OV
7-20 mA
0-2000
1000
50
3
Exponential
Any
0-1 OV
4-20 mA
0-2000
1100
50
4
Economizer
Proportional
15
0-1 OV
4-20 mA
0-1100
1100
50
5
Proportional
20
0-1 OV
4-20 mA
0- 900
900
50
6
Exponential
15
0-1 OV
4-20 mA
0-1100
1100
50
7
Exponential
20
0-1 OV
4-20 mA
0- 900
900
50
8
Health & Safety
Proportional
—
0-1 OV
4-20 mA
0-9999
5000
500
9
Parking/Air Intakes/
Loading Docks
Proportional
—
0-1 OV
4-20 mA
0-2000
700
50
LEGEND
ppm — Parts Per Million
Dehumidification of Fresh Air with DCV Control — Infor
mation from ASHRAE indicates that the largest humidity load
on any zone is the fresh air introduced. For some applications,
a field-installed energy recovery unit can be added to reduce
the moisture content of tire fresh air being brought into the
building when tire enthalpy is high. In most cases, the normal
heating and cooling processes are more than adequate to re
move the humidity loads for most commercial applications.
If normal rooftop heating and cooling operation is not ade
quate for the outdoor humidity level, an enei'gy I'ecoveiy unit
and/or a dehumidification option should be considei'ed.
Step 14 — Install Humidistat for Optional
MoistureMi$er’^'^ Package
— MoistuieMi$er dehu
midification package operation can be controlled by field in
stallation of a CaiTiei'-approved humidistat. To install the humi
distat perform the following procedure:
1. Locate humidistat on a solid interior wall in the condi
tioned space. Location should be a well ventilated area
to sense average humidity.
2. Route thermostat cable or equivalent single leads of col
ored wir'e from Humidistat terminals through conduit in
unit to the low voltage connection on the 2-pole terminal
strip (TB3) as shown in Fig. 4.3 and Fig. 44. See Fig. 45
for operational diagram.
29