Carrier 48TJ016-028 User Manual
Page 6
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

T T P ( 4 1 P L C S ^
0 ' - 3 ? / 8 '
1 3/8* 8iA. 08AIM HOLE
UNIT
STD UNIT
WEIGHT
ECONOMIZER
WEIGHT
CORNER
A
CORNER
B
CORNER
C
CORNER
D
DIMA
DIM B
DIMC
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
ft-in.
mm ft-in.
mm
tt-in.
mm
48TJD,
TJF024
1850
839
90
41
443
201
406
184
476
216
525
238
3-2
965
3-5
1041
1-8
508
48TJD,
TJF028
2000
907
90
41
471
214
428
194
526
239
574
260
3-2
965
3-5
1041
1-8
508
NOTES:
1. Refer to print for roof curb accessory dimensions.
2, Dimensions in ( ) are in millimeters.
3^ Center of Gravity.
Direction of airflow.
5. Ductwork to be attached to accessory roof curb only.
6. Minimum clearance:
• Rear: 7'-0" (2134) for coil removal. This dimension can be reduced to
4'-0" (1219) if conditions permit coil removal from the top.
• 4'-0" (1219) to combustible surfaces, all four sides (includes between
units).
' Left side: 4'-0" (1219) for proper condenser coil airflow.
' Front: 4'-0" (1219) for control box access.
• Right side: 4'-0" (1219) for proper operation of damper and power
exhaust if so equipped.
• Top: 6'-0" (1829) to assure proper condenser fan operation.
' Bottom: 14" (356) to combustible surfaces (when not using curb).
' Control box side: 3'-0" (914) to ungrounded surfaces, non-combustible.
• Control box side: 3'-6" (1067) to block or concrete walls, or other
grounded surfaces.
• Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the damper/
power exhaust as stated in Note #6, a removable fence or barricade
requires no clearance.
8. Dimensions are from outside of corner post. Allow O'-^/ie" (8) on each
side for top cover drip edge.
SECTfON A-A
Fig. 5 — Base Unit Dimensions; 48TJ024,028