DSE Model 71xx Series Control & Instrumentation System Mk2 Operators Manual

48

Part No. 057-113 71xx Series OPERATING MANUAL ISSUE 2 12/08/2010 ADM

Parameters with multiple choices use the following identification tables for the parameter values.

INPUT SOURCE LIST

7110

7120

0

User Configured

1

Alarm Mute

2

Alarm Reset

3

Alternative Configuration

4

Auto restore inhibit

X

5

Auto start inhibit

6

Auxiliary mains fail

X

7

Coolant Temperature Switch

8

Emergency Stop

9

External Panel Lock

10

RESERVED

11

Generator load inhibit

12

Lamp Test

13

Low Fuel Level Switch

14

RESERVED

15

Mains load inhibit

X

16

Oil Pressure Switch

17

Remote

Start Off Load

18

Remote Start On Load

19

Simulate mains available

X

20

Smoke Limiting

21

Transfer to Generator/Open Mains (7120)
Close Generator (7110)

22

Transfer to Mains/Open Generator (7120)
Open Generator (7110)

INPUT ACTION LIST

INPUT ARMING LIST

Index

Action

Index

Arming

0

Electrical Trip

0

Always

1

Shutdown

1

From Safety On

2

Warning

2

From Starting

3

Never

INPUT POLARITY LIST

Index

Action

OUTPUT POLARITY LIST

0

Close to Activate

Index

Arming

1

Open to Activate

0

Energise

1

De-energise

CAN DATA FAIL ACTION

Index

Action

CAN DATA FAIL ARMING

0

None

Index

Arming

1

Shutdown

0

From Safety On

2

Warning always latched

1

From Starting


Oil pressure Sensor selection

0

Not used

1

Digital closed for alarm

2

Digital open for alarm

3

VDO 5 Bar

4

VDO 10 Bar

5

Datacon 5 Bar

6

Datacon 10 Bar

7

Datacon 7 Bar

8

Murphy 7 Bar

9

CMB812

10

Veglia

11

User defined