DSE Model 71xx Series Control & Instrumentation System Mk2 Operators Manual

Part No. 057-113 71xx Series OPERATING MANUAL ISSUE 2 12/08/2010 ADM

27

6.2.3

ENGINE RUNNING


In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources :

Remote start input

Low battery run

Scheduled run

Mains failure (7120 only)

NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on

the engine.


Once the load has been transferred to the generator, it will not be automatically removed. To manually transfer the load back to
the mains (DSE7120) or to remove the load from the generator (DSE7110) either:

Press the auto mode

button to return to automatic mode. The set will observe all auto mode start requests and

stopping timers before beginning the Auto mode stopping sequence.

Press the stop button

6.2.4

STOPPING SEQUENCE


In manual mode the set will continue to run until either :

The stop button

is pressed – The set will immediately stop

The auto button

is pressed. The set will observe all auto mode start requests and stopping timers before

beginning the Auto mode stopping sequence.