DSE Model 71xx Series Control & Instrumentation System Mk2 Operators Manual
Part No. 057-113 71xx Series OPERATING MANUAL ISSUE 2 12/08/2010 ADM
27
6.2.3
ENGINE RUNNING
In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources :
•
Remote start input
•
Low battery run
•
Scheduled run
•
Mains failure (7120 only)
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on
the engine.
Once the load has been transferred to the generator, it will not be automatically removed. To manually transfer the load back to
the mains (DSE7120) or to remove the load from the generator (DSE7110) either:
•
Press the auto mode
button to return to automatic mode. The set will observe all auto mode start requests and
stopping timers before beginning the Auto mode stopping sequence.
•
Press the stop button
6.2.4
STOPPING SEQUENCE
In manual mode the set will continue to run until either :
•
The stop button
is pressed – The set will immediately stop
•
The auto button
is pressed. The set will observe all auto mode start requests and stopping timers before
beginning the Auto mode stopping sequence.