DSE Model 71xx Series Control & Instrumentation System Mk2 Operators Manual
Part No. 057-113 71xx Series OPERATING MANUAL ISSUE 2 12/08/2010 ADM
43
CONFIGURATION PARAMETERS – MAINS (Page 7)
7110
7120
MPU
CAN
MPU
CAN
701
AC system
0 (AC system)
X
X
702
Mains failure detection
On (1), Off (0)
X
X
703
Immediate mains dropout
On (1), Off (0)
X
X
704
Mains under voltage enable
On (1), Off (0
X
X
705
Mains under voltage trip level
0 V 00
X
X
706
Mains under voltage return
0 V
X
X
707
Mains over voltage enable
On (1), Off (0
X
X
708
Mains over voltage return
0 V
X
X
709
Mains over Voltage trip level
0 V
X
X
710
Mains under frequency trip enable
On (1), Off (0)
X
X
711
Mains under frequency trip level
0.0 Hz
X
X
712
Mains under frequency return
0.0 Hz
X
X
713
Mains over frequency trip enable
On (1), Off (0)
X
X
714
Mains over frequency return
0 Hz
X
X
715
Mains over frequency trip level
0.0 Hz
X
X
Generator and Mains AC System
0
2 Phase 3 wire (L1-L2)
1
2 Phase 3 wire (L1-L3)
2
3 Phase 3 wire
3
3 Phase 4 wire
4
3 Phase 4 wire delta
5
Single Phase 2 wire