beautypg.com

Winco DSE71xx Series User Manual

Page 43

background image

DSE Model 71xx Series Control & Instrumentation System Mk2 Operators Manual

Part No. 057-113 71xx Series OPERATING MANUAL ISSUE 2 12/08/2010 ADM

43

CONFIGURATION PARAMETERS – MAINS (Page 7)

7110

7120

MPU

CAN

MPU

CAN

701

AC system

0 (AC system)

X

X

702

Mains failure detection

On (1), Off (0)

X

X

703

Immediate mains dropout

On (1), Off (0)

X

X

704

Mains under voltage enable

On (1), Off (0

X

X

705

Mains under voltage trip level

0 V 00

X

X

706

Mains under voltage return

0 V

X

X

707

Mains over voltage enable

On (1), Off (0

X

X

708

Mains over voltage return

0 V

X

X

709

Mains over Voltage trip level

0 V

X

X

710

Mains under frequency trip enable

On (1), Off (0)

X

X

711

Mains under frequency trip level

0.0 Hz

X

X

712

Mains under frequency return

0.0 Hz

X

X

713

Mains over frequency trip enable

On (1), Off (0)

X

X

714

Mains over frequency return

0 Hz

X

X

715

Mains over frequency trip level

0.0 Hz

X

X

Generator and Mains AC System

0

2 Phase 3 wire (L1-L2)

1

2 Phase 3 wire (L1-L3)

2

3 Phase 3 wire

3

3 Phase 4 wire

4

3 Phase 4 wire delta

5

Single Phase 2 wire