CONFIGURATION PARAMETERS – INPUTS (Page 3) continued
7110
7120
MPU
CAN
MPU
CAN
331
Analogue input B sensor type
0 (sensor type)
332
Analogue input B sensor selection (temperature sensor list)
0 (temp sensor)
333
Analogue input B (set as digital) source (temperature sender)
0 (Input source)
334
Analogue input B polarity
0 (Polarity)
335
Analogue input B (set as digital) action (if source = user config)
0 (Action)
336
Analogue input B (set as digital) arming (if source = user config)
0 (Arming)
337
Analogue input B (set as digital) activation delay (if source = user
config)
0:00
338
Analogue input C sensor type
0 (sensor type)
339
Analogue input C sensor selection (temperature sensor list)
0 (pressure,
temperature or
percentage sensor)
340
Analogue input C (set as digital) source (flexible sender)
0 (Input source)
341
Analogue input C (set as digital) polarity
0 (Polarity)
342
Analogue input C (set as digital) action (if source = user config)
0 (Action)
343
Analogue input C (set as digital) arming (if source = user config)
0 (Arming)
344
Analogue input C (set as digital) activation delay (if source = user
config)
0:00
345
Oil pressure sender open circuit alarm enable
On (1), Off (0)
346
Temperature sender open circuit alarm enable
On (1), Off (0)
Continued overleaf...