6.1.3

ENGINE RUNNING

Once the engine is running and all starting timers have expired, the animated

icon is displayed

.


The generator is placed on load if configured to do so.

NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents excessive wear on

the engine.


If all start requests are removed, the stopping sequence will begin.

6.1.4

STOPPING SEQUENCE


The return delay timer operates to ensure that the starting request has been permanently removed and isn’t just a short term
removal. Should another start request be made during the cooling down period, the set will return on load.

If there are no starting requests at the end of the return delay timer, the load is removed from the generator to the mains supply
and the cooling timer is initiated.

The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly important where
turbo chargers are fitted to the engine.

After the cooling timer has expired, the set is stopped.