VT8300 Series
User Interface Guide
1/2 Setpoints
Occ. cool.
Standby cool.
Unocc. cool.
25.5 °C
24.0 °C
22.0 °C
20.5 °C
16.5 °C
26.5 °C
Occ. heat.
Standby heat.
Unocc. heat.
SETPOINT SETTINGS 1/2
SETPOINT PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Unocc. cool.
Default value: 26.5 °C (80 °F)
Unoccupied Cooling
Unoccupied cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby cool.
Default value: 25.5 °C (78 °F)
Standby Cooling
The value of this parameter should be set
between occupied and unoccupied cooling setpoints. Ensure
difference between standby and occupied value can be recovered in
a timely fashion when movement is detected in the zone.
Stand-by cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occ. cool.
Default value: 24.0 °C (74 °F)
Occupied Cooling
Cooling setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Occ. heat.
Default value: 22.0 °C (72 °F)
Occupied Heating
Heating setpoint range: 12.0 to 37.5 °C (54 to 100 °F).
Standby heat.
Default value: 20.5 °C (69 °F)
Standby Heating
The value of this parameter should be set between occupied and
unoccupied heating setpoints. Ensure difference between standby and
occupied value can be recovered in a timely fashion when movement is
detected in the zone.
Stand-by heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).
Unocc. heat.
Default value: 16.5 °C (62 °F)
Unoccupied Heating
Unoccupied heating setpoint range: 4.5 to 32.0 °C (40 to 90 °F).