Vt8300 series user interface guide – Viconics VT8300 Low Voltage User Interface Guide User Manual
Page 18

18
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-01
www.viconics.com
|
November 2014
©
2
01
4 V
ic
onic
s T
ec
hno
lo
gi
es
Inc
. A
ll r
ig
ht
s r
ese
rv
ed
.
VT8300 Series
User Interface Guide
2/7 Configuration
Auto fan func.
Fan menu
Auto mode
AS
On-Auto
Enabled
Standy mode
Abs
Standby diff.
2.0 C
Mode button
Normal
CONFIGURATION PARAMETERS SCREEN 2/7
PARAMETER DETAILS SCREEN 2/7
Configuration Parameters Default Value
Significance and Adjustments
Auto mode
Enables Auto menu for Mode button
Default value = On
Auto Mode
Enables auto function for the mode button
For sequences 2, 4, and 5 only
On = auto active (Off-Cool-Heat-Auto)
Off = auto not active (Off-Cool-Heat)
Fan menu
Default value = Local
Fan Speeds
User fan menu presented is dependent on selected fan sequence of
operation for the fan coil.
L-M-H: 3 Speed configuration using 3 fan relays.
L-H: 2 Speed configuration using 2 fan relays.
L-M-H-A: 3 Speed configuration with Auto fan speed mode using 3 fan
relays. Auto Mode operation is dependent on Auto Fan parameter.
L-H-A: 2 Speed configuration with Auto fan speed mode using 2 fan
relays. Auto Mode operation is dependent on Auto Fan parameter.
On-Auto: single Speed configuration. Auto is for Fan on demand/On is
On all the time.
Auto fan func.
Auto Fan Function
Default value: AS
Automatic Fan Function
Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
AS: auto Speed during occupied periods. Fan is always on during
occupied periods.
AS/AD: auto Speed/Auto Demand during occupied periods.