2/7 Configuration

Auto fan func.

Fan menu

Auto mode

AS

On-Auto

Enabled

Standy mode

Abs

Standby diff.

2.0 C

Mode button

Normal

CONFIGURATION PARAMETERS SCREEN 2/7

PARAMETER DETAILS SCREEN 2/7

Configuration Parameters Default Value

Significance and Adjustments

Auto mode
Enables Auto menu for Mode button
Default value = On

Auto Mode

Enables auto function for the mode button

For sequences 2, 4, and 5 only

On = auto active (Off-Cool-Heat-Auto)

Off = auto not active (Off-Cool-Heat)

Fan menu
Default value = Local

Fan Speeds

User fan menu presented is dependent on selected fan sequence of
operation for the fan coil.
L-M-H: 3 Speed configuration using 3 fan relays.

L-H: 2 Speed configuration using 2 fan relays.

L-M-H-A: 3 Speed configuration with Auto fan speed mode using 3 fan
relays. Auto Mode operation is dependent on Auto Fan parameter.

L-H-A: 2 Speed configuration with Auto fan speed mode using 2 fan
relays. Auto Mode operation is dependent on Auto Fan parameter.

On-Auto: single Speed configuration. Auto is for Fan on demand/On is
On all the time.

Auto fan func.
Auto Fan Function
Default value: AS

Automatic Fan Function

Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).

AS: auto Speed during occupied periods. Fan is always on during
occupied periods.

AS/AD: auto Speed/Auto Demand during occupied periods.