Viconics VWZS Application Guide User Manual
Viconics For Home
Table of contents
Document Outline
- 1.1. Viconics Part Number
- 1.2. Viconics Part Number
- Please refer to the following Viconics documents for detailed information and design guidelines for the wireless zoning system version:
- The system is fully scalable in terms of number of Zone controllers and RTU controllers used on the same network layer (BACnet MS-TP or Wireless models).
- Wireless controller systems overview:
- In this application, the VZ76xx controller(s) are the network coordinators to their own system. I.E. they are the network masters for each VZ72xx controller reporting to them. Each VZ76xx RTU controller and it’s associated VZ72xx zone controllers use the same PAN ID and channel. The range of PAN ID on all controllers to use is 251 to 500. This range is reserved for stand-alone (SA) system operation.
- Smallest System Supported
- Largest System Supported
- Number of Zones
- Number of RTUs
- Number of Zones
- Number of RTUs
- Single network of 127 nodes maximum
- 1 ZN reporting to
- 1 RTU Minimum
- 63 ZN reporting to
- 1 RTU Minimum
- (NS) Networked Systems operation. There is a high-level supervisory device installed and used in this configuration.
- In this application, a Viconics VWG and Jace-driver are the network coordinators for all controllers associated to the system and reporting their data point values.
- Each VZ76xx RTU controller and its associated VZ72xx zone controllers will use the same PAN ID and channel as the Viconics VWG and Jace-driver. The range of PAN ID on all controllers to use is 1 to 250. This range is reserved for the networked system (NS) operation.
- Smallest System Supported
- Largest System Supported
- Number of Zones
- Number of RTUs
- Number of Zones
- Number of RTUs
- Single Network trunk of 128 nodes maximum
- 1 ZN reporting to
- 1 RTU Minimum
- 126 ZN reporting to
- 1 RTU Minimum
- 63 ZN reporting to
- 63 RTU Maximum