PARAMETER DETAILS SCREEN 2/7

Configuration Parameters Default Value

Significance and Adjustments

Standby mode
Default value: Abs

Standby Mode

Choose which standby setpoints are used for control.

Abs: absolute Standby entered values are used for standby mode.

Offset: offset Occupied setpoints +/- Standby diff. used for standby

mode.

Standby diff.
Default value: 2 °C ( 3 °F )

Standby Difference

When Standby mode is Relative, standby setpoints are calculated as:

Standby cool = Cool setpoint + Standby diff.

Standby heat”= Heat setpoint - Standby diff.

Adjustable from 0.5 a 2.5 °C ( 1 - 5 °F )