PARAMETER DETAILS SCREEN 3/7

Configuration Parameters Default Value

Significance and Adjustments

Temp. occ. time
Default value: 2 hours

Temporary Occupancy Time

Temporary occupancy time with occupied mode setpoints when override
function is enabled.

When Terminal Equipment Controller is in unoccupied mode, function is
enabled with either the menu or UI2 configured as remote override input.

Range: 0 - 24 hours.

Deh. hysteresis
Default value: 5% RH

Humidity Control Hysteresis

Used only if dehumidification sequence is enabled:

Range: 2 to 20% RH (models with humidity sensor only).

Deh. max. cool
Default value: 100%

Maximum Dehumidification Cooling

Maximum cooling valve position when dehumidification is enabled. This
can be used to balance smaller reheat loads installed in regards to the
capacity of the cooling coil.

Range: 20 to 100 % (models with humidity sensor only).

Deh. lockout
Default value: Enabled

Dehumidification Lockout

Typically toggled through the network. This variable enables or disables
dehumidification based on central network requirements from the BAS
front end.

Enabled = Dehumidification Authorized

Disabled = Dehumidification Not Authorized

Models with humidity sensor only.