November 2014

©

2

01

4 V

ic

onic

s T

ec

hno

lo

gi

es

Inc

. A

ll r

ig

ht

s r

ese

rv

ed

.

VT8300 Series

User Interface Guide

3/7 Configuration

Temp. occ. time

Unocc. time

Standby time

2.0 hrs

0.0 hrs

0.5 hrs

Deh hysteresis

5.0% RH

Deh. max cool

100%

Deh. lockout

Enabled

CONFIGURATION PARAMETERS SCREEN 3/7

These parameters are only displayed on
models with built in humidity
sensor

PARAMETER DETAILS SCREEN 3/7

Configuration Parameters Default Value

Significance and Adjustments

Standby time
Default value: 0.5 hours

Standby Time

Time delay between the moment where the PIR cover detects

last movement in the area, and the time which the Terminal Equipment

Controller stand-by setpoints become active.

Range: 0.5 to 24.0 hours in 0.5 hours increments.

Unocc. time
Default value: 0.0 hours

Unoccupied Time

Time delay between the moment where the Terminal Equipment
Controller toggles to stand-by mode, and the time which the Terminal
Equipment Controller unoccupied mode and setpoints become active.

Factory value 0.0 hours: Setting this parameter to its default value of
0.0 hours disables the unoccupied timer. This prevents the Terminal
Equipment Controller to drift from stand-by mode to unoccupied mode
when PIR functions are used.

Range: 0.0 to 24.0 hours in 0.5 hours increments.