VT8300 Series

User Interface Guide

5/7 Configuration

Seq. operation

Pipe no.

Prop. band

Heat only

2

3.0

Purge sample

0.0 hrs

Purge open

1 min

CONFIGURATION PARAMETERS SCREEN 5/7

PARAMETER DETAILS SCREEN 5/7

Configuration Parameters Default Value

Significance and Adjustments

Prop. band
Default value: 3

Proportional Band Setting

Adjusts proportional band used by the Terminal Equipment Controller PI
control loop.

Note: default value of 3.0 gives satisfactory operation in

most normal installation cases. The use of a superior proportional band
different than the factory one is normally warranted in applications where
Terminal Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall mounted unit
where Terminal Equipment Controller is installed between return and
supply air feeds and is directly influenced by the supply air stream of unit.

Value

Effective Proportional Band

Fahrenheit

Celsius

3

3

1.2

4

4

1.7

5

5

2.2

6

6

2.8

7

7

3.3

8

8

3.9

9

9

5.0

10

10

5.6