beautypg.com

LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 75

background image

NeoTherm LC Boilers and Water Heaters

Page 71

Fig. 95 – Lead Lag Central Heat Configuration

3. Change the 4 mA water temperature to match

the lowest water temperature setting on the

Building Automation System or multiple

boiler control.

4. Change the 20mA water temperature to match

the highest water temperature setting on the

Building Automation System or Multiple

boiler control.

Note - Laars offers “gateways” to allow connections

to BACnet, LON, and other communications

protocols. See Section 9.6.

Job N - Building Automation or Multiple

Boiler 4-20 mA Modulation Control

(This is an individual function – do this on each of the controls.)

In this type of installation, the fan speed of each

boiler is changed or modulated by a source outside

of the boiler. All active burners must operate at the

same modulation rate while operating. The system

will not operate correctly if some of the burners

are being asked to operate at full rate while other

burners are operating at minimum rates.
Note - The system can also operate using 0 - 10V dc

using a converter (Laars part number CA006100.)

1. On each controller in the system, check

terminals 5 and 6 on TB7 to ensure that the

System sensor is not connected. (For this type

of operation, the Lead/Lag system is disabled.)

2. Connect the 4-20 mA input to each controller

in the system.
• On the Primary controller in each boiler,

connect to terminals 3 and 4 on TB7.

• On the Secondary controller in each boiler,

connect to terminals 7 and 8 on TB7.

3. Enable a central heat call for each control

on the system. This function must be set up

for each controller separately. This function

operates outside of the Lead/Lag system.

How to get there – Central Heat Enable
Home Page

NeoTherm LC Primary Screen
Primary Configuration Menu