C-PRO NANO HPR0 APPLICATION MANUAL

Page 5

1.1

I/O

For HPR0 a C-PRO NANO (INTRAbus) must be used with the following features .
Total analogical inputs: 4.

Total digital inputs: 5 (*). Total digital outputs: 6.

Total analogical outputs: 1 + 2 optionals (not present on this application).

(*) Note: A total number of 7 digital inputs are used in this application for this purpose n°2 analogue inputs will be used

as digital inputs.

I/O

Description

Analogue Inputs

A/I 1

Heating/cooling outlet / condit. (NTC)

A/I 2

A/I 3

Summer - Winter (ON-OFF potential-free contact)

A/I 4

External thermostat (ON-OFF potential-free contact)

Serial ports (RS 485 and
INTRABUS)

TTL (RS 485)

TTL with ext interf. EVIF becomes RS485 Modbus RTU

INTRAbus

towards c-pro EVCO instruments

Digital Inputs

D/I 1

High pressure switch (ON-OFF potential-free contact)

D/I 2

Low pressure switch (ON-OFF potential-free contact)

D/I 3

Geothermic circuit flow switch (ON-OFF potential-free contact)

D/I 4

Outlet circuit flow meter (ON-OFF potential-free contact)

D/I 5

Room thermostat (ON-OFF potential-free contact)

Analogue Outputs

A/O 1

PWM output not used

A/O 2

Optional (4-20 mA/0-10 V) : not present

A/O 3

Optional (4-20 mA/0-10 V) : not present

Digital Outputs

D/O 1

compressor 1

D/O 2

compressor 2

D/O 3

CYCLE INVERSION 4-WAY VALVE

D/O 4

Geothermic circuit pump

D/O 5

Heating/air conditioning outlet circuit pump

D/O 6

General alarm

N.B.: All contacts arriving at the controller inputs must be potential free contacts, without voltage.