4list of parameters, C-pro nano hpr0 application manual page 19 – EVCO c-pro nano HPR0 User Manual
Page 19

C-PRO NANO HPR0 APPLICATION MANUAL
Page 19
4
List of Parameters
The same parameters organisation used for c-pro CHILL can be maintained.
For the parameters and functions of the c-pro HPR0 application, see the following table.
As an example, the codes used with CHIL have been maintained (that will appear on the LED
display), but which will be “re-organised” regarding numbering depending on this new application.
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
USER PARAMETERS
PSd1
Modify the password to User level
0
-999
9999
UT
OUTLET SET
SPC1
Sets the summer outlet setpoint value
(cooling)
8.5
PC21
PC22
°C
UT
SSC1
Sets the summer outlet setpoint offset value
0.0
-20.0
20.0
°C
UT
SPH1
Sets the winter outlet setpoint value (heating)
44.0
PC23
PC24
°C
UT
SSH1
Sets the winter outlet setpoint offset value
0.0
-20.0
20.0
°C
UT
MAINTENANCE TECHNICIAN - INSTALLER PARAMETERS
PSd2
Sets the Maintenance technician - Installer
level password
0
-999
9999
IS-V
PM91
Sets the last date maintenance was performed
on the system (year)
2007
2007
2060
MA-F
PM92
Sets the last date maintenance was performed
on the system (month)
1
1
12
MA-F
PM93
Sets the last date maintenance was performed
on the system (day)
1
1
31
MA-F
CALIBRATION
PM81
Calibration of the heating water outlet
temperature probe
0.0
-20.0
20.0
°C
MA-CA
COMPRESSORS
PC04
Minimum time for which the compressor must
remain on even if switch-off has been
requested
20
0
999
Sec
IS-C
PC05
Minimum time for which the compressor must
remain off even if switch-on has been
requested
120
0
999
Sec
IS-C
PC06
Minimum time that must pass between two
switch-ons of the same compressor.
360
0
999
Sec
IS-C
PC07
Minimum time for switch-on of compressor 1
60
0
999
Sec
IS-C
PC08
Minimum time for switch-on of compressor 2
(winter mode)
10
0
20
Min
IS-C
PC09
Minimum time for switch-on of compressor 2
(summer mode)
60
0
999
Sec
IS-C
PC10
Compressor 1 block delay due to high
temperature
240
0
999
Sec
IS-C
OUTLET SET LIMITS
PC21
Outlet summer setpoint minimum value
5.0
-15.0
SPC1
°C
IS-R
PC22
Outlet summer setpoint maximum value
20.0
SPC1
23.0
°C
IS-R
PC23
Outlet winter setpoint minimum value
30.0
23.0
SPH1
°C
IS-R
PC24
Maximum value of the winter setpoint
44.0
SPH1
70.0
°C
IS-R
PUMPS and FLOW SWITCHES
PP04
Minimum time that must pass between the
switch-on of the pumps and switch-on of the
first compressor
60
1
999
Sec
IS-P
PP05
Minimum time that must pass between switch-
60
1
999
Sec
IS-P