beautypg.com

9 maintenance technician - installer menu, 10 manufacturer menu – EVCO c-pro nano HPR0 User Manual

Page 17

background image

C-PRO NANO HPR0 APPLICATION MANUAL

Page 17

3.9

Maintenance technician - Installer menu


The maintenance technician - installer level password or higher must be entered in order to
display/modify the parameters present in this branch.

Func

(FUNCTIONING Menu)

CAL

(CALIBRATION Menu)

CoMP

(COMPRESSORS Menu)

PuMP

(PUMPS Menu)

SEcu

(SAFETY Menu)

MAP

(PARAMETERS MAPS Menu)

I-O

(I/O STATE menu)

PSd2

(MAINTENANCE TECHNICIAN- INSTALLER Password)


In this menu it is possible to view the state of the various devices, inputs and outputs used by the
application.

In the FUNCTIONING menu it is allowed to set the data of the last maintenance operation
performed

In the CALIBRATION menu it is possible to set a correction to be made to the measurement of the
outlet probe in order to compensate any errors owing to wiring and positioning of the probe.

In the COMPRESSORS menu it is possible to set the parameters relative to functioning and the
protections of the compressors (timing, signalling delays, etc).

In the PUMPS menu it is possible to set the parameters relative to functioning and the protections of
the pumps (flow switches, timing, signalling delays, etc).

In the SAFETY DEVICES menu, find all parameters that concern the alarms and the management of
the safety conditions for the devices:

enablings

signal delays

type of reset...

The PARAMETERS MAPS menu can only be reached if the machine is OFF. In this menu it is
possible to save or reload the parameters from a programming key and, if necessary, to reset the
factory parameters. In this menu, after every operation, it is necessary to switch the instrument off
and back on again to make the modification operational.

3.10

Manufacturer Menu


The Manufacturer level password must be entered in order to display/modify the parameters present
in this branch. Moreover, this level can only be accessed with machine OFF (with just instrument
powered).

ConF

(SYSTEM menu)

PSd4

(MANUFACTURER Password)


This menu contains all machine configuration parameters.
It also allows to configure the logic of the inputs and outputs.