EVCO EVXV815P7 Installer manual User Manual

Page 45

background image

EVCO S.p.A.

EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124

page 45 of 66

u6

1

240

min

not

present

5

if parameter u11 is set at 1, maximum

duration of needle probe heating; see also

parameter u7

if parameter u11 is set at 2, duration of UV

light switch-on for the sterilisation cycle

u7

-50.0

99.0

°C/°F (1)

not

present

40.0

needle

probe

heating

end

temperature

(temperature detected by the needle probe);

also see parameter u6

u11

0

2

- - - -

not

present

0

utility managed by the output K5 (16)

0 = cabinet

light

(in

this

case,

the

AUXILIARY key and parameters i0 and

u2 will assume significance)

1 = needle probe heating (in this case, the

AUXILIARY key and parameters u6 and

u7 will assume significance)

2 = UV light (in this case, the AUXILIARY

key and parameter u6 will assume

significance)

Par.

Min.

Max.

Unit

EVXV802

EVXV812

EVXV805

EVXV815

Serial communication (MODBUS)

LA

1

247

- - - -

247

247

device address

Lb

0

3

- - - -

2

2

baud rate

0 = 2,400 baud

1 = 4,800 baud

2 = 9,600 baud

3 = 19,200 baud

LP

0

2

- - - -

2

2

Parity

0 = none

1 = odd

2 = even

Notes:

(1)

the unit of measurement depends on parameter P2

(2)

appropriately set the parameters relative to the regulators after modification of parameter P2

(3)

the time established with the parameter is counted also during the "on" status and during the "stand-by" status

(4)

the parameter differential is 2 °C/4 °F

(5)

on device switch-on (or cycle start), if the condenser temperature is already over that established with

parameter C7, parameter C8 will have no effect

(6)

defrosting is only enabled during storage, except for defrosting on blast chilling start and deep freezing start,

which can be established using parameter d4