“HACCP” FUNCTION (EVXV812 AND EVXV815

MODELS ONLY)

7.1

Foreword

Using the “HACCP” function, it is possible to memorise up to 9 events for each of the 3 HACCP alarms, after which the

most recent event overwrites the oldest.

The following table illustrates the information relative to the HACCP alarms, which the device can memorise.

Alarm

Code

Critical value

Date and time of

occurrence

Duration

temperature-controlled

blast chilling or deep

freezing not concluded

within

maximum

duration alarm

tiME

the

maximum

temperature detected by

the needle probe after

temperature-controlled

blast chilling of deep

freezing not concluded

within

maximum

duration

yes

from 1 min to 99 h and

59 min, partial if the

alarm is in progress

maximum

temperature

during storage alarm

AH

maximum

cabinet

temperature during the

alarm

yes

from 1 min to 99 h and

59 min, partial if the

alarm is in progress

power-cut during storage

alarm

PF

the cabinet temperature

at power supply restore

yes

from 1 min to 99 h and

59 min

To prevent repeated memorisation of power cut alarms (“PF” code), make sure that the device is in the "stand-by" or

"on" status before disconnecting the power supply.

If the duration of the power cut alarm (“PF” code) is such to cause a clock error (“rtc” code), the device does not

memorise the date or time the alarm occurred or its duration.

The HACCP LED supplies information relative to the memory status of the HACCP alarms of the device; see paragraph

10.1 “Signals”.

7.2

Displaying information relative to the HACCP alarms

Operate as follows:

1.

Make sure that the keyboard is not locked and that no procedure is in progress.

2.

Hold the DOWN key down for 1 s: the display will show the first label available.

3.

Press and release the UP or DOWN key to select “LS”.

4.

Press and release the BLAST CHILLING key: the display will show the most recent alarm code, i.e. one of the

codes stated in the table in paragraph 7.1 “Foreword”, followed by the number “1” (the higher the number that

follows the alarm code, the older the alarm).

To display the information relative to a HACCP alarm, operate as follows:

5.

Press and release the UP or DOWN key to select an alarm code, for example “AH3”.

6.

Press and release the BLAST CHILLING key: the HACCP LED will stop flashing and remain on permanently and

the display will show, for example, the following information in succession: