7
“HACCP” FUNCTION (EVXV812 AND EVXV815
MODELS ONLY)
7.1
Foreword
Using the “HACCP” function, it is possible to memorise up to 9 events for each of the 3 HACCP alarms, after which the
most recent event overwrites the oldest.
The following table illustrates the information relative to the HACCP alarms, which the device can memorise.
Alarm
Code
Critical value
Date and time of
occurrence
Duration
temperature-controlled
blast chilling or deep
freezing not concluded
within
maximum
duration alarm
tiME
the
maximum
temperature detected by
the needle probe after
temperature-controlled
blast chilling of deep
freezing not concluded
within
maximum
duration
yes
from 1 min to 99 h and
59 min, partial if the
alarm is in progress
maximum
temperature
during storage alarm
AH
maximum
cabinet
temperature during the
alarm
yes
from 1 min to 99 h and
59 min, partial if the
alarm is in progress
power-cut during storage
alarm
PF
the cabinet temperature
at power supply restore
yes
from 1 min to 99 h and
59 min
To prevent repeated memorisation of power cut alarms (“PF” code), make sure that the device is in the "stand-by" or
"on" status before disconnecting the power supply.
If the duration of the power cut alarm (“PF” code) is such to cause a clock error (“rtc” code), the device does not
memorise the date or time the alarm occurred or its duration.
The HACCP LED supplies information relative to the memory status of the HACCP alarms of the device; see paragraph
10.1 “Signals”.
7.2
Displaying information relative to the HACCP alarms
Operate as follows:
1.
Make sure that the keyboard is not locked and that no procedure is in progress.
2.
Hold the DOWN key down for 1 s: the display will show the first label available.
3.
Press and release the UP or DOWN key to select “LS”.
4.
Press and release the BLAST CHILLING key: the display will show the most recent alarm code, i.e. one of the
codes stated in the table in paragraph 7.1 “Foreword”, followed by the number “1” (the higher the number that
follows the alarm code, the older the alarm).
To display the information relative to a HACCP alarm, operate as follows:
5.
Press and release the UP or DOWN key to select an alarm code, for example “AH3”.
6.
Press and release the BLAST CHILLING key: the HACCP LED will stop flashing and remain on permanently and
the display will show, for example, the following information in succession: