EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 41 of 66
A8
0
240
min
15
15
maximum temperature alarm delay (“AH”
code) from the conclusion of evaporator fan
stop and storage start-up
A10
0
240
min
5
not
present in
EVXV802
model
5
not
present in
EVXV805
model
duration of a power cut such to cause the
power cut alarm to be memorised ( “PF”
code)when the power is supplied
0 = the alarm will not be signalled
AA
0
240
s
5
5
duration of buzzer activation on conclusion of
blast chilling and deep freezing
A11
0,1
15,0
°C/°F (1)
2,0
2,0
parameters A1 and A4 differential
A13
0
1
- - - -
1
not
present in
EVXV802
model
1
not
present in
EVXV805
model
memorisation of the temperature-controlled
blast chilling or temperature-controlled deep
freezing non concluded within maximum
duration alarm (“tiME” code)
1 = yes
Par.
Min.
Max.
Unit
EVXV802
EVXV812
EVXV805
EVXV815
Evaporator and condenser fan
F0
0
2
- - - -
1
1
evaporator fan activity during pre-cooling,
blast chilling and deep freezing
0 = off
1 = on; see also parameters F16 and F17
2 = parallel to the compressor; also see
parameters F9 and F17
F1
-50.0
99.0
°C/°F (1)
-1.0
-1.0
evaporator temperature above which the
evaporator fan is off during storage (only if
parameter F2 is set at 3); also see parameter
F8 (11)