Carrier 17/19EX User Manual
Page 433

SERVICE1 TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Motor Rated Load Amps
1 to 9999
AMPS
200
Motor Rated Line Voltage
1 to 9999
VOLTS
460
Meter Rated Line kW
1 to 9999
kW
600
Line Frequency
0=60 Hz/1=50 Hz
0/1
0
Compressor Starter Type
REDUCE/FULL
REDUCE
Condenser Freeze Point
–20 to 35
(–28.9 to 1.7)
DEG F
(DEG C)
34
(1.1)
Soft Stop Amps Threshold
40 to 100
%
100
Stop-to-Start Timer*
3 to 50
MIN
20
*Open-drive machines only. Standard stop-to-start time for hermetic machines is 3 minutes.
CL-8