Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
H. Normal Run with Reset, Temperature, Or Demand
Primary Message
Secondary Message
Probable Cause/Remedy
Running — Reset Active
4-20MA Signal
Reset program active based upon Config
table setup.
Running — Reset Active
Remote Sensor Control
Running — Reset Active
CHW Temp Difference
Running — Temp Control
Leaving Chilled Water
Default method of temperature control.
Running — Temp Control
Entering Chilled Water
ECW control activated on Config table.
Running — Temp Control
Temperature Ramp Loading
Ramp loading in effect. Use Service1 table to
modify.
Running — Demand Limited
By Demand Ramp Loading
Ramp loading in effect. Use Service1 table to
modify.
Running — Demand Limited
By Local Demand Setpoint
Demand limit setpoint is
<
actual demand.
Running — Demand Limited
By 4-20MA Signal
Demand limit is active based on Config table
setup.
Running — Demand Limited
By CCN Signal
Running — Demand Limited
By Loadshed/Redline
Running — Temp Control
Hot Gas Bypass
Hot Gas Bypass is energized. See surge pre-
vention in the
section.
Running — Demand Limited
By Local Signal
Active demand limit manually overridden or
Status01 table.
Running — Temp Control
Ice Build Mode
Machine is running under Ice Build tempera-
ture control.