Table 15 — nih waterbox cover weights, Table 15 – Carrier 17/19EX User Manual
Page 339

NIH — Nozzle-in-Head
* The 150 psig (1034 kPa) waterbox cover weights are included in the dry weight shown in
† Two different waterbox covers are present on 2-pass machines. The weight shown in this table
represents the weight of the waterbox cover that contains the nozzles. A blank waterbox cover is also
present on 2-pass units. The weight of the blank waterbox cover is identical to the weight of the same
size marine waterbox cover. Refer to
Table 15 — NIH Waterbox Cover Weights*
Heat Exchanger
Size
Passes
Design Maximum
Water Pressure
Cooler
Condenser
psi
kPa
lb
kg
lb
kg
41 – 48
1
150
1034
2997
1361
1735
788
300
2068
4225
1918
2510
1140
2
†
150
1034
2984
1355
1885
856
300
2068
4188
1901
2590
1176
3
150
1034
3035
1378
1777
807
300
2068
4244
1927
2539
1153
51 – 57
1
150
1034
–
–
2032
923
300
2068
–
–
2940
1335
2
†
150
1034
–
–
2649
1203
300
2068
–
–
3640
1653
3
150
1034
–
–
–
–
300
2068
–
–
–
–