B. timing out or timed out – Carrier 17/19EX User Manual
Page 311

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
B. Timing Out or Timed Out
Primary Message
Secondary Message
Probable Cause/Remedy
Ready To Start In XX
Min
Unoccupied Mode
Time schedule for PIC is unoccupied. Machines will
start only when occupied.
Ready To Start In XX
Min
Remote Contacts Open
Remote contacts have stopped machine. Close con-
tacts to start.
Ready To Start In XX
Min
Stop Command In Effect
Chiller START/STOP on Status01 manually forced to
stop. Release value to start.
Ready To Start In XX
Min
Recycle Restart Pending
Machine in recycle mode.
Ready To Start
Unoccupied Mode
Time schedule for PIC is UNOCCUPIED. Machine will
start when occupied. Make sure the time and date have
been set on the Service menu.
Ready To Start
Remote Contacts Open
Remote contacts have stopped machine. Close con-
tacts to start.
Ready To Start
Stop Command In Effect
Chiller START/STOP on Status01 manually forced to
stop. Release value to start.
Ready To Start In XX
Min
Remote Contacts Closed
Machine timer counting down unit. Ready for start.
Ready To Start In XX
Min
Occupied Mode
Machine timer counting down unit. Ready for start.
Ready To Start
Remote Contacts Closed
Machine timers complete, unit start will commence.
Ready To Start
Occupied Mode
Machine timers complete, unit start will commence.
Startup Inhibited
Loadshed In Effect
CCN loadshed module commanding chiller to stop.
Ready To Start In XX
Min
Start Command In Effect
Chiller START/STOP on Status01 has been manually
forced to start. Machine will start regardless of time
schedule or remote contact status.