C. in recycle shutdown, Click here for table 8c — in recycle shutdown – Carrier 17/19EX User Manual
Page 312

Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
C. In Recycle Shutdown
Primary Message
Secondary Message
Probable Cause/Remedy
Recycle Restart
Pending
Occupied Mode
Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart
Pending
Remote Contact Closed
Unit in recycle mode, chilled water temperature is not high
enough to start.
Recycle Restart
Pending
Start Command In
Effect
Chiller START/STOP on Status01 manually forced to start,
chilled water temperature is not high enough to start.
Recycle Restart
Pending
Ice Build Mode
Machine in ICE BUILD mode. Chilled Water/Brine Tem-
perature is satisfied for Ice Build Setpoint temperature.