Charge Refrigerant into Machine

The 17/19EX machine may have the refrigerant already charged in the utility vessels. If

machine is not shipped fully charged, refrigerant is shipped separately to conform with

transportation regulations. The 17/19EX may be ordered with a nitrogen holding charge of

15 psig (103 kPa). Evacuate the entire machine, and charge machine from refrigerant cylinders.

The full refrigerant charge on the 17/19EX will vary with machine components and design

conditions, indicated on the job data specifications. An approximate charge may be found in

17/19EX

Physical Data

section. The full machine charge is printed on the machine identification

label.

Always operate the condenser and chilled water pumps during charging operations to

prevent freeze-ups. Use the Controls Test Terminate Lockout to monitor conditions and start

the pumps.

If the machine has been shipped with a holding charge, the refrigerant will be added through

CAUTION

CAUTION

!

The transfer, addition, or removal of refrigerant in spring isolated machines may
place severe stress on external piping if springs have not been blocked in both
up and down directions.